TP-6069 6/03A-4 Appendix
Appendix C Generator Set Output Ratings Procedure

Kohler Co. develops the kilowatt output rating of aKohler r

marine generator set based upon the calculations

specified in ISO 3046 and ISO 8528-1. The calculations

correct for environmental variables encountered in a

generator set installation. Figure 1 outlines the

calculations. Figure2 contains examples of how heat

variables affect generator set ratings.

Generator Output corrected = Generator Output observed x Correction Factor

Output power is expected to be within ±5% of the specified rating when corrected to reference conditions.

Correction factors are determined using the following formulas:

1. For naturally aspirated compression-ignition engines (power limited by excess air):

C.F.= [1.175 (29.2 / Dry Barometer in. Hg)1(Temperature _F + 460/537).75 --.175]

x Alternator Efficiency Reference / Alternator Efficiency Observed

2. For turbocharged compression ignition engines:

C.F.= [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)2--.175]

x Alternator Efficiency Reference / Alternator Efficiency Observed

3. For turbocharged and intercooled compression ignition engines:

C.F.= [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)1.2 --.175]

x Alternator Efficiency Reference / Alternator Efficiency Observed
Reference conditions:
Temperature:77_F; Pressure: 29.2 in. Hg dry barometer.
Kohler sound shield increases ambient intake air approx. 12_F
Approximate derates:
Temperature:approximately 1% per 10_F (turbocharged engines have a greater derate);
Pressure (altitude): approximately 4% per 1000 ft. (1 in. Hg)

Figure 1 Generator Output

5.5
5.6
5.7
5.8
5.9
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
7.0
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
8.0
75 80 85 90 95 100 105 110 115 120
Temperature(_F)
77
60 Hz
50 Hz
KEY

Figure 2 Example: 6.5EFOZ/8EOZ kW Derates (ISO 3046/ISO 8258-1)