Section 8 Reconnection/Adjustments

8.1 Four-Lead Reconnection

The following information illustrates the reconnection of four-lead generator sets. In all cases, conform to the National Electrical Code (NEC).

NOTICE

Voltage reconnection. Affix a notice to the generator set after

breaker. Application of two single-pole circuit breakers does not conform to NEC requirements for supplying a 200--240-volt load, even if the breakers are mechanically attached together. Leads L1 and L2 are for different phases; never connect them together.

L0 (Neutral)

L0

reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.

8.1.1100--120-Volt Configurations

If the installation requires a factory two-pole circuit breaker, do not connect the load-side terminals of the circuit breaker together; see Figure 8-1. If the installation requires a 100--120-volt, 2-wire system, use a single-pole circuit breaker. See Figure 8-2. When connecting stator phase leads together, size the output lead (L1) to handle the amperage. Use a jumper lead on the line side of the circuit breaker to balance the load of the generator set.

L0 (Neutral)

L0

 

Ground

Load

Side

Line

Side

4 3 2 1 Stator Leads

60 Hz

L0--L1 100--120 Volt

L0--L2 100--120 Volt

GRD.

L1

Single-Pole

Circuit

Breaker

50 Hz

100--120 Volt

100--120 Volt

GRD.

Ground

L1

L2

Load

Figure 8-2 100--120-Volt, 2-Wire Configuration

L0 (Neutral)

L0

Side

 

 

Two-Pole

Line

Circuit

 

Side

Breaker

 

Jumper lead

4 3 2 1

Ground

Load

Side

Line

Side

GRD.

L2

L1

Factory

Two-Pole

Circuit

Breaker

Figure 8-1 100--120-Volt, 3-Wire Configuration

8.1.2100--120/200--240-Volt Configurations

The 100--120/200--240-volt configuration does not use a jumper lead. If the unit was originally wired for straight 100--120 volt, 3-wire, remove the jumper lead (see Figure 8-1 for location). Select a two-pole circuit

100-120/200-240-Volt,

43 2 1 3-Wire

Stator Leads

 

 

60 Hz

50 Hz

L0--

L1

100--

120 Volt

100--

120 Volt

L0--

L2

100--

120 Volt

100--

120 Volt

L1--

L2

200--

240 Volt

200--

240 Volt

 

 

 

Figure 8-3

100

--120/200 240-Volt, 3-Wire--

Configuration

TP-6069 6/03

Section 8 Reconnection/Adjustments 67