Lennox Hearth MPD-33 Series Vertical Termination Systems Roof, Vent Section Length Chart

Models: MPD-35 Series MPD-45 Series MPD-33 Series MPD-40 Series

1 32
Download 32 pages 35.84 Kb
Page 11
Image 11
VERTICAL TERMINATION SYSTEMS (ROOF)

VERTICAL TERMINATION SYSTEMS (ROOF)

Figure 16, and Figures 26 through 30 on pages 14 and 15 and their associated Vertical Vent Tables illustrate the various verti- cal venting configurations that are possible for use with these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex pipe may also be used. A Vertical Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.

Both these vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls is speci- fied in ANSI Z223.1-(latest edition) (In Canada, the current CAN-1 B149 installation code) by major building codes. Always consult your local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer to

Figure 4 on page 5).

Vertical (Straight) Installation

Determine the number of straight vent sections required. 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46- 1/2" (1181 mm) net section lengths are avail- able. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Refer to the Vent Section Length Chart.

SV4.5CGV-1

SV4.5FA OR

Termination

SV4.5FB Flashing

 

 

AND SV4.5SC

 

STORM COLLAR

 

 

 

1" (25.4 mm)

 

 

 

Minimum

 

 

 

Clearance to

 

 

 

Combustibles

 

 

 

*SV4.5VF

 

 

 

Firestop/Spacer

40'

Max

SV4.5L6/12/24/36/48

(12.2

M)

Vent Sections

 

 

 

 

 

 

*When using Secure Flex,

 

 

 

use Firestop/Spacer

 

 

 

SF4.5VF

VENT SECTION LENGTH CHART

Nominal

6

 

12

24

36

 

48

T

Section Length

 

 

O

(inches)

 

 

 

 

 

 

 

T

Net Section

4-1/2

 

10-1/2

22-1/2

34-1/2

46-1/2

A

Length (inches)

 

L

Height of Vent

 

Number of Vent Sections

 

Q

 

 

 

 

 

 

 

 

 

T

inches

ft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

4.5

0.375

1

 

0

0

0

 

0

1

 

 

 

 

 

 

 

 

 

 

9

0.75

2

 

0

0

0

 

0

2

 

 

 

 

 

 

 

 

 

 

10.5

0.875

0

 

1

0

0

 

0

1

15

1.25

1

 

1

0

0

 

0

2

19.5

1.625

2

 

1

0

0

 

0

3

 

 

 

 

 

 

 

 

 

 

 

 

 

21

1.75

0

 

2

0

0

 

0

2

 

 

 

 

 

 

 

 

 

 

22.5

1.875

0

 

0

1

0

 

0

1

 

 

 

 

 

 

 

 

 

 

25.5

2.125

1

 

2

0

0

 

0

3

31.5

2.625

0

 

3

0

0

 

0

3

 

 

 

 

 

 

 

 

 

 

34.5

2.875

0

 

0

0

1

 

0

1

 

 

 

 

 

 

 

 

 

 

37.5

3.125

1

 

1

1

0

 

0

3

 

 

 

 

 

 

 

 

 

 

43.5

3.625

0

 

2

1

0

 

0

3

 

 

 

 

 

 

 

 

 

 

45

3.75

0

 

0

2

0

 

0

2

 

 

 

 

 

 

 

 

 

 

46.5

3.875

0

 

0

0

0

 

1

1

 

 

 

 

 

 

 

 

 

 

49.5

4.125

1

 

0

2

0

 

0

3

 

 

 

 

 

 

 

 

 

 

51

4.25

1

 

0

0

0

 

1

2

 

 

 

 

 

 

 

 

 

 

55.5

4.625

0

 

1

2

0

 

0

3

 

 

 

 

 

 

 

 

 

 

57

4.75

0

 

0

1

1

 

0

2

 

 

 

 

 

 

 

 

 

 

66

5.25

0

 

2

2

0

 

0

4

67.5

5.625

0

 

0

3

0

 

0

3

69

5.75

0

 

0

0

2

 

0

2

 

 

 

 

 

 

 

 

 

 

72

6

1

 

0

3

0

 

0

4

 

 

 

 

 

 

 

 

 

 

73.5

6.125

1

 

0

0

2

 

0

3

79.5

6.625

0

 

1

0

2

 

0

3

81

6.75

0

 

0

0

1

 

1

2

 

 

 

 

 

 

 

 

 

 

90

7.5

0

 

2

1

0

 

1

4

 

 

 

 

 

 

 

 

 

 

91.5

7.625

0

 

0

2

0

 

1

3

93

7.75

0

 

0

0

0

 

2

2

96

8

1

 

0

1

2

 

0

4

 

 

 

 

 

 

 

 

 

 

97.5

8.125

1

 

0

0

0

 

2

3

102

8.5

2

 

0

0

0

 

2

4

103.5

8.625

0

 

0

0

3

 

0

3

108

9

1

 

0

0

3

 

0

4

 

 

 

 

 

 

 

 

 

 

114

9.5

0

 

2

0

0

 

2

4

 

 

 

 

 

 

 

 

 

 

117

9.75

1

 

0

5

0

 

0

6

118.5

9.875

1

 

1

0

3

 

0

5

 

 

 

 

 

 

 

 

 

 

126

10.5

0

 

0

1

3

 

0

4

 

 

 

 

 

 

 

 

 

 

130.5

10.875

1

 

0

1

3

 

0

5

 

 

 

 

 

 

 

 

 

 

135

11.25

0

 

0

6

0

 

0

6

138

11.5

0

 

0

0

4

 

0

4

 

 

 

 

 

 

 

 

 

 

139.5

11.625

0

 

0

0

0

 

3

3

 

 

 

 

 

 

 

 

 

 

142.5

11.875

1

 

0

0

4

 

0

5

 

 

 

 

 

 

 

 

 

 

 

 

VENT SECTION LENGTH CHART

 

 

Nominal Section

6

 

12

24

36

48

T

Length (inches)

 

O

 

 

 

 

 

 

 

 

 

T

Net

Section

 

 

 

 

 

 

4-1/2

 

10-1/2

22-1/2

34-1/2

46-1/2

A

Length (inches)

 

 

 

 

 

 

 

 

 

 

L

Height of Vent

 

Number of Vent Sections

Q

 

 

 

 

 

 

 

 

 

inches

 

ft

 

 

 

 

 

 

T

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

144

 

12

1

 

0

0

0

3

4

 

 

 

 

 

 

 

 

 

 

150

 

12.5

0

 

1

0

0

3

4

 

 

 

 

 

 

 

 

 

 

154.5

 

12.875

1

 

1

0

0

3

5

 

 

 

 

 

 

 

 

 

 

160.5

 

13.375

0

 

2

0

0

3

5

 

 

 

 

 

 

 

 

 

 

172.5

 

14.375

0

 

0

0

5

0

5

 

 

 

 

 

 

 

 

 

 

177

 

14.75

1

 

0

0

5

0

6

 

 

 

 

 

 

 

 

 

 

183

 

15.25

0

 

1

0

5

0

6

 

 

 

 

 

 

 

 

 

 

186

 

15.5

0

 

0

0

0

4

4

 

 

 

 

 

 

 

 

 

 

190.5

 

15.875

1

 

0

0

0

4

5

 

 

 

 

 

 

 

 

 

 

196.5

 

16.375

0

 

1

0

0

4

5

 

 

 

 

 

 

 

 

 

 

205.5

 

17.125

0

 

1

1

5

0

7

 

 

 

 

 

 

 

 

 

 

207

 

17.25

0

 

0

0

6

0

6

 

 

 

 

 

 

 

 

 

 

211.5

 

17.625

1

 

0

0

6

0

7

 

 

 

 

 

 

 

 

 

 

217.5

 

18.125

0

 

1

0

6

0

7

 

 

 

 

 

 

 

 

 

 

229.5

 

19.125

0

 

0

1

6

0

7

 

 

 

 

 

 

 

 

 

 

232.5

 

19.375

0

 

0

0

0

5

5

 

 

 

 

 

 

 

 

 

 

237

 

19.75

1

 

0

0

0

5

6

 

 

 

 

 

 

 

 

 

 

241.5

 

20.125

0

 

0

0

7

0

7

246

 

20.5

1

 

0

0

7

0

8

252

 

21

0

 

1

0

7

0

8

264

 

22

0

 

0

1

7

0

8

276

 

23

0

 

0

0

8

0

8

279

 

23.25

0

 

0

0

0

6

6

 

 

 

 

 

 

 

 

 

 

280.5

 

23.375

1

 

0

0

8

0

9

 

 

 

 

 

 

 

 

 

 

283.5

 

23.625

1

 

0

0

0

6

7

 

 

 

 

 

 

 

 

 

 

289.5

 

24.125

0

 

1

0

0

6

7

 

 

 

 

 

 

 

 

 

 

301.5

 

25.125

0

 

0

1

0

6

7

310.5

 

25.875

0

 

0

0

9

0

9

315

 

26.5

1

 

0

0

9

0

10

325.5

 

27.125

0

 

0

0

0

7

7

330

 

27.5

1

 

0

0

0

7

8

336

 

28

0

 

1

0

0

7

8

345

 

28.75

0

 

0

0

10

0

10

 

 

 

 

 

 

 

 

 

 

349.5

 

29.125

1

 

0

0

10

0

11

 

 

 

 

 

 

 

 

 

 

372

 

31

0

 

0

0

0

8

8

 

 

 

 

 

 

 

 

 

 

376.5

 

31.375

1

 

0

0

0

8

9

 

 

 

 

 

 

 

 

 

 

379.5

 

31.625

0

 

0

0

11

0

11

418.5

 

34.875

0

 

0

0

0

9

9

423

 

35.25

1

 

0

0

0

9

10

465

 

38.75

0

 

0

0

0

10

10

 

 

 

 

 

 

 

 

 

 

Figure 16

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

11

Page 11
Image 11
Lennox Hearth MPD-33 Series, MPD-45 Series Vertical Termination Systems Roof, on page Vertical Straight Installation