Lennox Hearth MPD-45 Series, MPD-40 Series, MPD-35 Series HORIZONTAL VENT FIGURES/TABLES continued

Models: MPD-35 Series MPD-45 Series MPD-33 Series MPD-40 Series

1 32
Download 32 pages 35.84 Kb
Page 20
Image 20
(Square termination SV4.5HT-2 shown.)

HORIZONTAL VENT FIGURES/TABLES (continued)

**Wall Firestop/Spacer Figure 40 - Top Vent - THREE 90 DEGREE ELBOWS (SV4.5HF)

H1

H2

*When using Secure Flex,

 

*Ceiling

 

Firestop/Spacer

use Firestop/Spacer

 

 

(SV4.5VF)

SF4.5VF

 

 

 

**When using Secure

V

 

 

Flex, use Firestop/Spacer

 

 

SF4.5HF

 

 

H

 

 

TABLE K

 

 

H + H1 + H2 Maximum

H Maximum

V Minimum

feet

(meters)

feet

(meters)

feet

(meters)

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + H + H1 + H2 = 40 feet (12.2 m) Max.

H = 8 feet (2.438 meters) Max.

H + H1+ H2 = 20 feet (6.096 meters) Max.

Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.

See Table 4 on page 18 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 39 - Rear Vent - THREE 90 DEGREE ELBOWS (Square termination SV4.5HT-2 shown.)

 

*When using Secure Flex,

 

use Firestop/Spacer

 

SF4.5VF

H1

**When using Secure

Flex, use Firestop/Spacer

 

SF4.5HF

 

*Ceiling

 

Firestop/Spacer

 

(SV4.5VF)

**Wall Firestop/Spacer

H

 

(SV4.5HF)

V1

 

V

**Wall Firestop/Spacer

TABLE L

H Maximum

V Minimum

 

 

 

 

 

feet

 

(meters)

feet

(meters)

5

 

(1.524)

Elbow Only

5

 

(1.524)

1

(0.305)

10

 

(3.048)

2

(0.610)

15

 

(4.572)

3

(0.914)

20

 

(6.096)

4

(1.219)

 

H + H1 = 20 feet (6.096 m) Max.

V + V1+ H + H1 = 40 ft. (12.192 m) Max.

Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed

(Square termination SV4.5HT-2 shown.)

(SV4.5HF)

5 feet of (H) horizontal run, up to a maxi- mum horizontal run of 20 feet.

See Table 4 on page 18 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 40 - Top Vent - THREE 90 DEGREE ELBOWS

An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 35.

20

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Page 20
Image 20
Lennox Hearth MPD-45 Series, MPD-40 Series HORIZONTAL VENT FIGURES/TABLES continued, Square termination SV4.5HT-2shown