DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and
Step 1. FRAMING
Frame these appliances as illustrated in Figure 9 on page 8, unless the appliance is to be installed in a corner. See Figure 10 on page 8 for corner framing installations. All framing details must allow for a minimum clearance to combustible framing members as shown in
Table 2.
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.
Headers may be in direct contact with the appliance top spacers but must not be sup- ported by them or notched to fit around them. All construction above the appliance must be self supporting. DO NOT use the appliance for structural support.
The fireplace should be secured to the side fram- ing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front. See Figure 6. Use 8d nails or their equivalent.
Side | Unit Nailing Flange | |
(No clearance to | ||
Framing | ||
combustible | ||
| framing is required) | |
Left Side Front Corner of Fireplace Shown | ||
(Right Side Requirements the Same) | ||
Unit Being Secured By Its Nailing Flanges | ||
| To The Framing | |
Note: The nailing flanges, combustible members | ||
and screw heads located in areas directly adjacent | ||
to the nailing flanges, are EXEMPT from the 1/2” | ||
clearance to combustible requirements for the | ||
firebox outer wrapper. Combustible framing may be | ||
in direct contact with the nailing flanges and may | ||
be located closer than 1/2” from screw heads and | ||
the firebox wrapper in areas adjacent to the nailing | ||
flanges. Frame the opening to the exact dimensions | ||
specified in the framing details of this manual. |
Figure 6
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside of the right side framing as shown in Figure 7. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. All appli- ances are
Right Side
Front Corner of
Fireplace Framing
3" (76 mm)
Figure 7
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.