Lennox Hearth MPD-33 Series, MPD-45 Series, MPD-40 Series HORIZONTAL VENT FIGURES/TABLES continued

Models: MPD-35 Series MPD-45 Series MPD-33 Series MPD-40 Series

1 32
Download 32 pages 35.84 Kb
Page 19
Image 19
HORIZONTAL VENT FIGURES/TABLES (continued)

HORIZONTAL VENT FIGURES/TABLES (continued)

H1H

TABLE H

H+H1 Maximum

H Maximum

V Minimum

feet (meters)

feet (meters)

feet (meters)

(1.524)

 

 

*When using Secure Flex, use Firestop/Spacer SF4.5HF

**When using Secure Flex, use Firestop/Spacer SF4.5VF

V

*Wall

Firestop/Spacer

(SV4.5HF)

Figure 37 - Rear Vent - TWO 90 DEGREE ELBOWS **Ceiling Firestop/Spacer

(SV4.5VF)

5

 

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

 

V + H + H1 = 40 feet (12.2 m) Max.

 

 

H = 8 feet (2.438 meters) Max.

 

H + H1 = 20 feet (6.096 meters) Max.

Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of

(V)vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.

See Table 4 on page 18 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 37 - Rear Vent - TWO 90 DEGREE ELBOWS

(Square termination SV4.5HT-2 shown.)

H1

*When using Secure Flex, use Firestop/Spacer SF4.5HF

**Note - When using Secure Flex, use Firestop/Spacer SF4.5VF

*Wall Firestop/Spacer

 

 

TABLE J

 

(SV4.5HF)

 

H + H1 Maximum

V Minimum

H

 

 

feet

(meters)

feet

(meters)

 

 

 

 

3

(0.914)

Elbow Only

 

V

5

(1.524)

1

(0.305)

 

10

(3.048)

2

(0.610)

 

 

 

 

15

(4.572)

3

(0.914)

*Wall Firestop/Spacer

 

20

(6.096)

4

(1.219)

(SV4.5HF)

 

V + H + H1 = 40 feet (12.2 m) Max.

**Ceiling

 

 

H + H1 = 20 ft. (6.096 m) Max.

 

 

 

 

 

Firestop/Spacer

 

 

 

 

 

(SV4.5VF)

 

 

 

 

 

Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.

An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 35. See Table 4 on page 18 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 38 - Top Vent - TWO 90 DEGREE ELBOWS (Square termination SV4.5HT-2 shown.)

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

19

Page 19
Image 19
Lennox Hearth MPD-33 Series, MPD-45 Series HORIZONTAL VENT FIGURES/TABLES continued, Rear Vent - TWO 90 DEGREE ELBOWS