Lennox Hearth MPD-33 Series, MPD-45 Series, MPD-40 Series Pilot for Honeywell Millivolt Gas Valve

Models: MPD-35 Series MPD-45 Series MPD-33 Series MPD-40 Series

1 32
Download 32 pages 35.84 Kb
Page 31
Image 31
Pilot for Honeywell Millivolt Gas Valve

b. Attach manometer to the manifold side pressure test fitting and verify manifold pres- sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.

c. Convert the pilot orifice as follows (see Figures 62, 63 and 64 ):

Note - Use extra care not to engage the orifice strip with the 7/16" open end wrench (contact- ing the orifice strip could cause strip distortion rendering the pilot inoperative). Also avoid wrench contact to any of the other pilot parts.

Use a 7/16" open end wrench and turn the pilot hex fitting counter-clockwise 1/4 turn. (See

Figure 62).

Note - The orifice strip tab may be randomly located on any side of the hex fitting.

d. Push the orifice strip tab all the way against

the hex fitting to align the appropriate gas type

orifice (see Figures 63 and 64). The type of

gas for which the pilot is set, is, the gas type

Pilot for Honeywell Millivolt Gas Valve

(Loosening of Hex Fitting For Orifice Strip Tab Positioning)

Hood

Hood Alignment

7/16 in. Open End Wrench

 

Orifice Strip Tab

 

Take Care Not to Contact the Orifice Strip Tab

Figure 62

with the Hex Fitting Wrench - Distortion of the Tab

May Render the Pilot Inoperative.

 

 

 

 

 

Pilot for Honeywell Millivolt Gas Valve

 

Orifice Strip Tab Position Identification

 

For LP/Propane and Natural Gas

shown on the tab.

e. Retighten, clockwise, the pilot hex fitting

until the pilot hood aligns with the thermo-

couple and thermopile as indicated by the

arrows shown in Figure 62.

LP/Propane Gas Position -

1/16 in. Hole, LP and

Red Color shown on tab

L

P

Natural Gas Position -

NAT shown on tab

NAT

Figure 63

Top View of Hex Fitting and Orifice Strip Tab

 

 

 

 

 

 

Pilot for Honeywell Millivolt Gas Valve

 

Orifice Strip Tab Positioning

 

Pilot Hood Position After

 

Loosening Hex Fitting 1/4 Turn

 

Orifice Strip Tab

 

Push Tab to Set

 

Gas Type Usage

 

Note - Orifice Strip Tab May

 

Be Randomly Located On Any

Figure 64

Side Of The Hex Fitting

 

 

 

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

31

Page 31
Image 31
Lennox Hearth MPD-33 Series, MPD-45 Series Pilot for Honeywell Millivolt Gas Valve, Orifice Strip Tab Positioning