VERTICAL VENT FIGURES/TABLES
(continued)
|
| TABLE C |
|
| H1 | ||
H+H1 Maximum | H Maximum | V Minimum | |||||
| |||||||
feet | (meters) | feet | (meters) | feet | (meters) |
| |
5 | (1.524) | 2 | (0.610) | 1 | (0.305) | *Ceiling | |
| (3.048) |
| (1.219) |
| (0.610) | Firestop/Spacer | |
10 | 4 | 2 | (SV4.5VF) | ||||
15 | (4.572) | 6 | (1.829) | 3 | (0.914) |
| |
20 | (6.096) | 8 | (2.438) | 4 | (1.219) | **Wall | |
|
|
|
|
|
| ||
| V + V1 | + H + H1 = 40 feet (12.2 m) Max |
| Firestop/Spacer | |||
|
| (SV4.5HF) | |||||
| H = 8 feet (2.438 meters) Max. |
| |||||
|
| V1 | |||||
| H + H1 = 20 feet (6.096 meters) Max. |
|
|
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to aV maximum horizontal run of 20 feet.
Figure 29 - Rear Vent - THREE ELBOWS
*When using Secure Flex, use Firestop/Spacer SF4.5VF
**When using Secure Flex, use Firestop/Spacer SF4.5HF
*Ceiling
Firestop/Spacer
(SV4.5VF)
H
TABLE D
H + H1 Maximum |
| V Minimum | |
feet | (meters) | feet | (meters) |
5 | (1.524) |
| Elbow Only |
5 | (1.524) | 1 | (0.305) |
10 | (3.048) | 2 | (0.610) |
15 | (4.572) | 3 | (0.914) |
20 | (6.096) | 4 | (1.219) |
H + H1 = 20 feet (6.096 m) Max.
V + V1 + H + H1 = 40 ft. (12.192 m) Max.
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system. See Figure 35.
Figure 30 - Top Vent - THREE ELBOWS
|
| *Ceiling |
| |
V | 1 | Firestop/Spacer | **Wall | |
(SV4.5VF) | ||||
| Firestop/Spacer | |||
|
|
| (SV4.5HF) | |
|
| H |
| |
|
| H1 | V | |
|
|
| ||
|
| *When using Secure Flex, |
| |
|
| use Firestop/Spacer |
| |
|
| SF4.5VF |
| |
|
| **When using Secure |
| |
|
| Flex, use Firestop/Spacer |
| |
|
| SF4.5HF |
|