Troubleshooting Guide
Possible Trouble 2
The compressor does not operate.
Is settingNO
Temp. set lower than Room • Select the setting Temp. to lower Number.
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
Is the voltage No.10 |
| NO | Is the voltage N0.7 of |
| NO | Is the Unit for 3 minutes | NO | |||||||
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
| ||||||||
of IC01M 0V? |
|
|
| IC01M DC 5V? |
|
|
| delay? | ||||||
| YES |
|
|
|
| YES |
|
|
|
| YES | |||
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Check the |
|
|
| • Exchange IC01M. |
|
|
| • Wait 3 Minutes. |
•Check the wiring Diagram.
• Exchange MAIN
PCB Ass'y.
Possible Trouble 3
The compressor always operate.
Is the wire connection of | NO |
| • Connect LEAD Wire to |
| |
|
| ||||
|
| ||||
|
|
|
| ||
|
|
|
| ||
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
YES
• Check the
29Room Air Conditioner