5.0OPERATION

Operation

5.0OPERATION

The Liebert LDM is a factory-installed option to provide monitoring of the main breaker, branch cir- cuit breakers and subfeed breakers. It may be installed in the Liebert PPC Precision Power Center, Liebert FDC, Liebert FPC and Liebert RDC Remote Distribution Cabinet.

Software available on Liebert’s Web site (see 5.3 - Downloading the Software) can be installed on a desktop or laptop computer (PC) to monitor status and configure breaker parameters and alarm set- points. These monitoring and configuration functions are described in 5.4 - Using the Monitor Tool and 5.5 - Using the Configuration Tool.

The Liebert LDM monitors and displays the parameters listed in Table 5.

Table 5 Parameters monitored for breakers

 

 

Displayed and monitored for each:

 

 

Panelboard

Panelboard main

SqD I-Line

Subfeed

 

branch

circuit breaker and

panelboard

circuit

Parameters

circuit breaker

SqD I-Line panelboard

circuit breaker

breaker

Voltage

Line-to-line

Line-to-neutral

Phase Current

Neutral Current

Ground Current

kVA

kW

kW-Hours

Percent Load

Power Factor

Crest Factor

Voltage Total Harmonic Distortion (THD)

Current Total Harmonic Distortion (THD)

Circuit identification and status of each breaker are also displayed. Parameters are updated every 500msec.