Operation
5.4.2Monitor Menu Options
The Monitor window has a menu bar at the top with a
|
|
|
|
|
|
| Menu options |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
Table 7 | Monitor menu options | ||||||
|
|
|
|
|
| ||
| Menu Option | Function | |||||
| File Menu |
|
|
|
| ||
| • | Exit |
| Terminates the monitoring session and closes the Monitor program. | |||
|
|
|
|
|
|
| |
| View Menu |
|
|
|
| ||
| • | Event Logs | Opens the Event Log window, allowing users to view a list of events for Panel A or Panel B or | ||||
|
|
|
|
| system. Events are listed in order of occurrence, starting with the most recent. | ||
| • | Breakers |
| Updates the status of all branch breakers for the selected panel in the Breaker Status area. | |||
| • | Subfeeds | Updates the status of all subfeed breakers for the selected panel in the Breaker Status area. | ||||
|
|
|
|
|
| ||
| Dump Menu |
|
|
| |||
| • | Readings | Downloads a .csv file with main breaker, branch circuit breaker and subfeed readings. The file | ||||
|
|
|
|
| may be viewed with a spreadsheet program such as Microsoft Excel. | ||
| • | Event Log | Downloads a .csv file with the event log stored on the BCB. The file may be viewed with a | ||||
|
|
|
|
| spreadsheet program such as Microsoft Excel. | ||
| • | Configuration | Downloads a .txt file with the configuration file stored on the BCB. The file includes scaling data, | ||||
|
|
|
|
| Panelboard A and B configurations, branch circuit values and CT ratio settings. | ||
| Alarms Menu |
|
|
| |||
| Choose one of three | ||||||
| Note that alarms sent over Modbus are latched independent of changes performed in the Alarms menu. | ||||||
| • | Raw |
| The raw alarm state is the instantaneous state of the alarm. It is not filtered and has no | |||
|
|
|
|
| hysteresis. When Raw is selected, an alarm is active whenever the latest reading exceeds the | ||
|
|
|
|
| setpoint and is cleared as soon as the reading returns to a level within the setpoint range. | ||
| • | Filtered |
| The filtered alarm uses the hysteresis interval to suppress transient alarms. A filtered alarm is | |||
|
|
|
|
| cleared after the alarm condition remains cleared for longer than the hysteresis interval. | ||
| • | Latched |
| Latched alarms behave like filtered alarms that get stuck on. A latched alarm stays active until | |||
|
|
|
|
| the alarm is manually cleared. | ||
| • | Clear All |
| Clears all latched alarms for the selected panel. Any alarm condition that is still active is latched | |||
|
|
|
|
| again after the hysteresis interval passes. | ||
| Help Menu |
|
|
|
| ||
| • | About |
| Displays information about Liebert Distribution Monitoring. | |||
|
|
|
|
|
|
|
|
5.4.3Panel Status and Real-Time Clock
The Panel Status area displays:
•The name of the Liebert LDM in the Unit box.
•The currently selected panel in the Panel box.
To choose a different panel, click on the panel name or the A/B button. If the selected panel has any active alarms, the panel name appears in white text with a red background.
The
• Click the Set button to force the