Operation
5.4.4Main Breaker Status
The Main Breaker Status area displays RMS current, percent load (PCT), total harmonic distortion (THD), crest factor (CF),
Metered energy usage for the panel
The metered energy usage for the panel is also displayed in kilowatt hours (kWh), as shown above. To clear all metering information, click the Reset All kWh button.
! CAUTION
Exercise care before using the Reset All kWh button, which resets the kWh usage for the main breaker as well as all branch breakers and subfeed breakers on the panel.
5.4.5Breaker Status
The Breaker Status area displays detailed status for every branch or subfeed breaker on the selected panel. The information may appear in a table or as icons, depending on the whether the Table or Icons button is active (see 5.4.6 - Mode Buttons).
The example below shows the table format with details for each breaker: type and rating, percent load, individual phase current in amps (I1, I2, I3), power, apparent power (VA), power factor (PF) and accumulated kilowatt hours (kWh.)
5.4.6Mode Buttons
Mode buttons at the bottom of the Monitor window allow users to download Monitor readings to a file, toggle the display between branch and subfeed breakers, toggle between table and icon views of breaker status data and view the Event Log. Additionally, Emerson Network Power technical person- nel may control the
|
| Subfeeds/Breakers | Icons/Table |
|
| button | button |
Table 8 | Monitor mode buttons |
| |
|
|
| |
Button | Function |
| |
|
|
| |
Dump |
| Converts the Monitor readings into a spreadsheet format (.csv file format). | |
|
|
| |
Subfeeds/Breakers | Toggles between the subfeed and branch breaker displays. The button label changes | ||
when the display is changed. |
| ||
|
|
| |
Icons/Table | Toggles between the tabular and icon views. The button label changes when the display is | ||
changed. |
| ||
|
|
| |
Events |
| Displays the Event Log dialog box. |
|
| Viewable only if the diagnostic registry key has been installed on the PC. Used by Emerson | ||
(not shown above) | Network Power technical personnel for diagnostic purposes only. |
|
20