6.0 SPECIFICATIONS

ELECTRICAL

Voltage

120 - 240 VAC (-13% to +6%)

 

 

Frequency

50 and 60Hz

 

 

Control Transformers Rating

1A for Branch Circuits and Subfeeds

(Secondary Winding)

5A for Main Input Breaker

BSM Current

0.25A to 50A

 

 

CT Accuracy

2% for 1A to 50A

5% for 0.25A to 1A

 

Minimum Current

200mA

 

 

ENVIRONMENTAL

 

 

 

Humidity

0-95%

 

 

Temperature (Non-Operating)

-68°F to 158°F (-20°C to 70°C)

 

 

Temperature (Operating)

32°F to 104°F (0°C to 40°C)

 

 