Mechanical Considerations

4.0MECHANICAL CONSIDERATIONS

4.1Determining Placement in the Conditioned Space

Liebert XDVs should be placed above or on top of the cabinets that generate the greatest amount of heat. If heat loads are dispersed evenly throughout the room, the Liebert XDV modules may be spread out accordingly.

The Liebert XDV is engineered to fit atop computer enclosure cabinets. Figure 8, below, illustrates the unit’s dimensions and the location of pipes, the fan tray and power connections. (An optional kit is available to permit suspending the Liebert XDV from either Unistruts or from the overhead struc- ture; see 5.2 - Suspended Mounting Method.).

Figure 8 Liebert XDV dimensions

PH

Liebert XDV With

Pre-charged Option

(all dimensions except piping height are the same as for the hard-piped setup, see Table 2)

W

DT

DF

DB

H

DPN000770

Page 2, Rev. 6

Liebert XDV With Hard-piped Arrangement

Table 2

Dimensional data

 

Illustration

 

 

 

Measurement,

Key

 

Dimension

 

in (mm)

DT

 

Depth Top

 

39-1/2 (1003)

 

 

 

 

 

DB

 

Depth Bottom

 

29-5/8 (752)

 

 

 

 

 

W

 

Width

 

22-7/8 (581)

 

 

 

 

 

H

 

Height

 

14 (356)

 

 

 

 

 

 

 

Piping Height,

 

18-5/8 (473)

 

 

hard-piped

 

PH

 

 

 

 

Piping Height,

 

19-5/8 (498)

 

 

 

 

 

one-shot option

 

 

 

 

 

 

 

 

 

 

DF

 

Depth Front

 

9-7/8 (250)

 

 

 

 

 