Piping
6.6.1Refrigerant Charge—Pre-Charged Option
Liebert XDVs with the
Do not remove the pipe caps or plugs before the unit is ready for connection to Liebert XD Piping. Do not disconnect
6.7Field Installation of Liebert Flex Pipe Kit on Liebert XDV
If you are not performing a service installation or a
Liebert Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters). Connec- tion style to the unit end may be straight or 90 degrees. Connection to the prefab piping assembly is a threaded coupler. For data on acquiring the correct kit for your installation, see Table 7.
Figure 27 Liebert XD Flex Pipe dimensions—straight and 90-degree connections
Connection | Connection |
to Prefabricated | |
to Prefabricated | Piping assembly |
Piping assembly |
|
|
| Length | |
Length | 4, 6, | 8 or 10 feet | |
(1.2, 1.8, | 2.4 or 3 meters) | ||
4, 6, 8 or 10 feet | |||
|
|
(1.2, 1.8, 2.4 or 3 meters)
Straight Connection
Connection to XD Cooling Unit
90° Connection to XD Cooling Unit
DPN000780
Pg. 2, Rev. 1
6.8Connecting Liebert XD Flex Pipe to Liebert XDV Modules
1.Remove the caps on the supply and return lines on the top of the Liebert XDV.
2.Lubricate the threads, diaphragm and
3.Connect the
4.Make sure the Schrader valve is properly oriented; refer to the label on the top of the Liebert XDV.
5.Hold the backup hex nut with a wrench while tightening the swivel nut.
6.Tighten the swivel nut on the female coupling until it is seated or a definite resistance is felt.
7.Once a definite bottoming resistance is felt (as in metal to metal), place a mark lengthwise from the swivel nut to the backup hex and tighten the swivel nut on the female coupling an additional 1/4 turn.
8.Tighten both the supply fittings and the return fittings to
9.Mark the female and male coupler with for future reference.
25