Specifications

11.0SPECIFICATIONS

Table 5

Liebert XDV10 specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XDV10BK--*; XDV10DK--*

 

XDV10BT--*; XDV10DT--*

 

XDV10BS--*; XDV10DS--*

 

 

 

XDV10BKP-*; XDV10DKP-*

 

XDV10BTP-*; XDV10DTP-*

 

XDV10BSP-*; XDV10DSP-*

 

 

 

XDV10BK-E*; XDV10DK-E*

 

XDV10BT-E*; XDV10DT-E*

 

XDV10BS-E*; XDV10DS-E*

 

 

 

XDV10BKPE*; XDV10DKPE*

 

XDV10BTPE*; XDV10DTPE*

 

XDV10BSPE*; XDV10DSPE*

 

 

 

XDV10BKR-*; XDV10BKRE*

 

XDV10BTR-*; XDV10BTRE*

 

XDV10BSR-*; XDV10BSRE*

 

 

 

XDV10DKR-*; XDV10DKRE*

 

XDV10DTR-*; XDV10DTRE*

 

XDV10DSR-*; XDV10DSRE*

 

Models

 

60 Hz

 

60 Hz

50 Hz

 

50 Hz

 

 

 

 

 

 

 

Cooling Capacity

 

Nominal (98ºF [37ºC] EAT): 10kW / 2.8 Tons

Nominal (98ºF [37ºC] EAT): 8kW / 2.3 Tons

 

Maximum (106ºF [41ºC] EAT): 11.8kW/3.4 Tons

Maximum (116ºF [47ºC] EAT): 11.8kW/3.4 Tons

 

 

 

Conditions

 

Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and

 

50ºF (10ºC) or lower dew point, rear air inlet.

 

 

 

Electrical Requirements

 

 

 

 

 

 

 

Input

 

120V model: 1ph-60 Hz

 

230V model:

230V model: 1ph-50 Hz

 

 

 

1ph-60 Hz

 

 

 

 

 

 

 

 

Input power connections

 

 

2 power connections, each model

 

 

 

 

 

 

 

 

 

 

Full Load Amps

 

120V model: 2.0A

 

 

230V model: 1.0A

 

 

 

 

 

 

 

 

Power consumption,

 

180

 

190

190

 

190

 

nominal, watts

 

 

 

 

 

 

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

 

Height – unit only

 

14 (355) not including pipe connections

 

 

 

 

 

 

 

 

Height – including hard

 

 

18-5/8 (473)

 

 

 

pipe connections

 

 

 

 

 

 

 

 

 

 

 

 

Height – including one-

 

 

19-5/8 (498)

 

 

 

shot connections

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

 

22-7/8 (581)

 

 

 

 

 

 

 

 

 

 

Depth – Top

 

 

39-1/2 (1003)

 

 

 

 

 

 

 

 

 

 

Depth – Bottom

 

 

29-5/8 (752)

 

 

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

 

Unit only

 

 

77 (35)

 

 

 

 

 

 

 

 

 

 

Shipping weight

 

 

125 (57)

 

 

 

 

 

 

 

 

Installed, with refrigerant

 

 

79 (36)

 

 

 

 

 

 

 

 

 

Number of fans

 

2

 

2

2

 

2

Airflow, Nominal,

 

1000 (1699) with rear inlet. Bottom inlet airflow

833 (1415) with rear inlet. Bottom inlet airflow

 

may be less, depending on restrictions inside

may be less, depending on restrictions inside

ft3/ min (m3/ hr)

 

 

cabinet

 

 

 

 

cabinet

 

 

 

 

 

 

 

 

 

 

 

Audible noise

 

78 dBa sound power

73 dBa sound power

Pipe Connections (without Liebert Flex Pipe)

 

 

 

 

 

 

Refrigerant supply

 

1/2" OD, Cu, (optional 1/2" threaded coupler flex piping)

from Liebert XDP/ XDC

 

 

 

 

 

 

 

 

 

Refrigerant return

 

5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)

to Liebert XDP/ XDC

 

 

 

 

 

 

 

 

Serviceable Parts

 

 

 

Fans and electrical components

 

Cabinet Exterior Finish

 

Black, matte finish, heat-fused powder coat

Options

 

 

 

 

 

 

 

 

Condensate sensing

 

 

 

Dry contact outgoing signal

 

 

(factory-installed)

 

 

 

 

 

 

 

 

 

 

 

 

Pre-Charged Refrigerant

 

R-134a Refrigerant, one-shot connections

 

 

 

 

 

 

 

 

 

Agency

 

 

 

 

 

 

 

 

 

Approvals

 

CSA 60Hz

 

 

CSA 50Hz

 

CE 50Hz

 

 

 

 

 

 

 

 

* = Revision level of unit

 

 

 

 

 

 