Lincoln Electric IM463-A manual Table RECOMMENDED INPUT WIRE AND FUSE SIZES

Models: IM463-A

1 34
Download 34 pages 14.19 Kb
Page 10
Image 10
Table 1

Table 1

RECOMMENDED INPUT WIRE AND FUSE SIZES (1)

Input Voltage /

Input Ampere Rating

Type 75°C Cu (Copper)

Grounding Wire

Fuse Size

Frequency

on Nameplate

Wire in Conduit

Cu (Copper)

(Super Lag)

 

 

 

 

 

 

208V

/ 60 Hz

130

1/0

6

200

 

 

 

 

 

 

230V

/ 60 Hz

117

1/0

6

175

 

 

 

 

 

 

460V

/ 60 Hz

59

4

8

100

 

 

 

 

 

 

575V

/ 60 Hz

47

6

8

75

200V /

50/60 Hz

138

2/0

4

225

220V /

50/60 Hz

125

1/0

6

200

380V /

50/60 Hz

73

4

6

125

400V /

50/60 Hz

69

4

8

100

415V /

50/60 Hz

66

4

8

100

440V /

50/60 Hz

63

4

8

100

500V /

50/60 Hz

55

6

8

75

 

 

 

 

 

 

(1)For a 600A / 44V / 100% duty cycle output in a 40°C ambient location. Refer to your local or national electrical code for other conditions.