Model MGT Gate Edge Transmitter Setup

Linear’s Model MGT Gate Edge Transmitter can be used with the RE-2 for obstacle detection. When the gate edge sensor triggers the MGT transmitter, the RE-2 can be programmed to activate Relay #2 which would in turn, activate the obstacle input of the gate operator.

Press: Obstacle Facility ID

Obstacle: 0 = No MGT obstacle transmitter (default) 1 = MGT obstacle transmitter used

Facility: Facility code 0-15 of MGT transmitter ID = 5-digit ID number of transmitter

NOTE: The Facility and ID entries are not required if Obstacle is set to “0”.

Remote Keypad Address

Default: 3

If a Linear Model AM-KP is used as a remote keypad the ADDRESS switch in the remote keypad needs to match the “address” setting in the RE-2. For most installations, simply set the remote keypad’s ADDRESS switch to “3” to match the RE-2 default setting. If required, use the following programming PPN to change the address number.

Press: Address

Address: 0 = Remote keypad disabled 1-6 = Keypad address 1-6

NOTE: After changing the keypad address, restart the system using the RESTART button.

Sense Input Alternate Function

Defaults:

 

SENSE #1 = SENSE

 

SENSE #2 = SENSE

Each of the two SENSE inputs can be independently programmed to act as INHIBIT inputs. As an INHIBIT input, as long as the input is grounded, access can not be granted for that input’s relay (1 or 2). A typical application would be connection of an external timer or service switch to temporarily prevent visitors from activating the access device.

Press: Input Type

Input: 1 = SENSE #1 2 = SENSE #2

Type: 0 = Input will perform as SENSE 1 = Input will perform as INHIBIT

Keypad Lockout Count

Default: 5 Tries

The Keypad Lockout Count sets the number of incorrect code entry attempts required to place the keypad in “lockout” for a one minute period. During “lockout” the keypad will not accept any code entries. The Keypad Lockout Count effects both the main and remote keypads.

Press: Count

Count = 2-7 Incorrect entries

Anti-passback Time

Default: Off

The Anti-passback feature prevents the same entry code or transmitter from being used to gain access more than once during the set time.

Press: Time

Time: 0 = No anti-passback

1-4 = Anti-passback time (in minutes)

Modem Ring Detect On/Off

Default: On

The RE-2’s built-in modem monitors the telephone line for telephone rings. When the Modem Ring Detect is enabled, the modem will answer the telephone if two consecutive telephone calls occur within 30 seconds. The Modem Ring Detect can be disabled, this will also disable any computer based programming of the RE-2.

Press: Detect

Detect: 0 = Ring detect OFF 1 = Ring detect ON

Keypad Beeps On/Off

Default: On

The default setting causes the main keypad to beep when each key is pressed. The beeps can be disabled.

Press: Keypad Beeps

Keypad Beeps: 0 = Beeps OFF

1 = Beeps ON

Relay #1 Tone On/Off

Default: Off

The default setting does not cause the annunciator to sound when Relay #1 is activated. The Relay #1 activation tone can be enabled.

Press: Relay #1 Tone

Relay #1 Tone: 0 = Tone OFF

1 = Tone ON

Relay #2 Tone On/Off

Default: Off

The default setting does not cause the annunciator to sound when Relay #2 is activated. The Relay #2 activation tone can be enabled.

Press: Relay #2 Tone

Relay #2 Tone: 0 = Tone OFF

1 = Tone ON

Relay Tone Duration

Default: 1 Second

The default setting causes the annunciator to sound for 1 second when Relay #1 or Relay #2 is activated (if the tones are enabled). The length of the activation annunciation can be changed.

Press: Tone Length

Tone Length = Tone length in Seconds 1-15

Voice Synthesizer On/Off

Default: On

When the voice synthesizer is on the RE-2 will sound voice prompts during operation and programming. If the voice synthesizer is off, the system will sound beeps to indicate conditions. The HELP button will announce “Enter code or press call button to contact resident” regardless of this setting.

The beeps produced when the voice synthesizer is off are:

1 Short beep — Keypad key pressed

2 Short beeps — Programming entry was valid

1 Long beep — Programming entry was invalid

Press: Voice

Voice: 0 = Voice synthesizer OFF 1 = Voice synthesizer ON

Automatic Daylight Savings Time Clock Adjustment On/Off Default: On

The RE-2’s internal clock used for controlling system functions and time stamping of the event log automatically adjusts for daylight savings time. For areas where daylight savings time is not observed, this feature may be disabled.

Press: Daylight Savings

Daylight Savings:0 = Daylight Savings Adjust OFF

1 = Daylight Savings Adjust ON

Automatic Door/Gate Open Time

Default: Not Set

Each control relay can be programmed for automatic activation. One or two Time Zones can be assigned to a relay. The relay will activate and remain latched during the active period of the Time Zone.

Press: Relay 1st Time Zone 2nd Time Zone

Relay: 1 = Relay #1 2 = Relay #2

1st Time Zone = Time Zone 1-7

2nd Time Zone = Time Zone 1-7 (enter “0” if the 2nd time zone is not used)

19

Page 21
Image 21
Linear RE-2 Press Obstacle Facility ID, Press Address, Press Input Type, Press Count, Press Detect, Press Keypad Beeps