Lochinvar 400 - 801 service manual Flame Sequence, Auto Reset, High Limit, Fan Low, Fan Speed Low

Models: 400 - 801

1 48
Download 48 pages 44.71 Kb
Page 39
Image 39

Service Manual

3Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flame

 

 

 

 

 

 

 

 

 

 

 

Sequence

 

• Check supply voltage for proper polarity.

 

 

 

 

(will require a manual

 

 

 

 

 

 

• Check external wiring for voltage feedback.

 

 

reset once the condition

 

 

 

The flame detector circuit is seeing a flame

• Check the flame rod and make sure it is clean.

 

 

has been corrected.

signal while no flame is present.

 

 

Press the RESET button

• Check the internal wiring for bad connections.

 

 

on the SMART

 

 

 

 

• Replace main control board.

 

 

 

 

 

 

SYSTEM display to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

Knight

XL

Installation

and

Operation

Manual

 

 

for the proper piping methods for the Knight XL boiler.

 

 

• Check 120 vac to boiler pump motor on a call for

 

 

heat. If voltage is not present, check wiring back to

 

 

the main control board.

 

 

 

 

 

 

 

 

 

• Replace the main control board if necessary.

 

 

Auto Reset

The outlet water temperature has exceeded

• If 120 vac is present on a call for heat and the boiler

the setting of the automatic reset high limit.

pump is not operating, replace the pump.

 

 

 

 

High Limit

 

 

 

 

 

 

 

 

 

 

 

• If the system pump is a variable speed pump, ensure

 

 

 

 

that the system flow is not less than the boiler flow.

 

 

• If operating on something other than an outlet sensor,

 

 

check temperature setting of the main control board.

 

 

• If the optional manual reset high limit has tripped,

 

 

check setting of the device.

 

 

 

 

 

 

 

 

 

• Check resistance of water sensors and compare to

 

 

Table 3-2A on page 35 of this manual. Replace

 

 

sensor if necessary.

 

 

 

 

 

 

 

 

 

• Replace high limit.

 

 

 

 

 

 

 

 

 

 

 

The actual fan RPM is 30% lower than what

• Vent/air intake lengths exceed the maximum allowed

 

is being called for.

lengths. Refer to Section 3 - General Venting of the

Fan Low

 

Knight XL Installation and Operation Manual for

 

proper lengths.

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

 

 

 

Fan Speed Low

 

• Check

for

obstruction or

blockage

in

the

vent/air

 

intake pipes or at terminations.

 

 

 

 

 

 

(will require a manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset once the condition

 

• Check

the wiring connections at

the

fan

and at the

has been corrected.

 

 

main control board.

 

 

 

 

 

 

 

Press the RESET button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the SMART

 

• Replace the fan.

 

 

 

 

 

 

 

SYSTEM display to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset.)

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blown fuse.

• Replace fuse F2 on the control board, see page 33

 

of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 39
Image 39
Lochinvar 400 - 801 service manual Flame Sequence, Auto Reset, High Limit, Fan Low, Fan Speed Low