Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

GV/Relay

 

• Check wiring harness connection at the gas valve and

Fail

 

at the main control board.

 

(will require a manual

The main control board did not detect the

 

 

 

reset once the condition

• Replace the gas valve wire harness.

 

has been corrected. Press

gas valve.

 

 

 

the RESET button on the

 

• Replace the gas valve.

 

 

SMART SYSTEM display

 

 

 

 

to reset.)

 

• Replace the main control board.

 

 

 

 

 

 

• Vent/air intake lengths exceed the maximum allowed

 

 

lengths. Refer to Section 3 - General Venting of the

Fan High

 

Knight XL Installation

and Operation

Manual for

 

proper lengths.

 

 

OR

 

 

 

 

 

 

 

Fan Speed High

 

• Check for obstruction

or blockage in

the vent/air

(will require a manual

 

The actual fan RPM is 30% higher than what

intake pipes or at terminations.

 

reset once the condition

 

is being called for.

 

 

 

has been corrected. Press

 

• Check the wiring connections at the fan and at the

the RESET button on the

 

 

main control board.

 

 

SMART SYSTEM display

 

 

 

 

 

 

 

to reset.)

 

• Replace the fan.

 

 

 

 

 

 

 

 

• Replace the main control board.

 

 

 

 

Sensor Open

 

• Check the sensors and their associated wiring.

(will require a manual

 

Repair or replace the sensor or wiring if damaged.

reset once the condition

 

 

 

 

has been corrected. Press

Either the inlet water or outlet water

• Measure the resistance of the sensors and compare

the RESET button on the

temperature sensor has been disconnected.

the resistance to the tables on page 35 of this

SMART SYSTEM display

 

manual.

 

 

to reset.)

 

 

 

 

 

 

• Replace the sensor if necessary.

 

 

 

 

Sensor Shorted

 

• Check the sensors and their associated wiring.

 

Repair or replace the sensor or wiring if damaged.

(will require a manual

 

 

 

 

 

reset once the condition

Either the inlet water or outlet water

• Measure the resistance of the sensors and compare

has been corrected. Press

the RESET button on the

temperature sensor has been shorted.

the resistance to the tables on page 35 of this

SMART SYSTEM display

 

manual.

 

 

 

 

 

 

to reset.)

 

• Replace the sensor if necessary.

 

 

 

 

 

 

 

 

 

Louver Proving

 

 

 

 

Sw

 

 

 

 

(will require a manual

 

• Check function of remote devices.

 

reset once the condition

An optional remote proving switch is not

 

 

 

has been corrected. Press

making.

• Check for loose or misplaced jumper if auxiliary

the RESET button on the

 

proving switch is not installed.

 

SMART SYSTEM display

 

 

 

 

to reset.)

 

 

 

 

 

 

 

 

 