Lochinvar 400 - 801 Low 24 vac, Watch Dog Error, Write EEProm, CRC Parameters, No Error Stored

Models: 400 - 801

1 48
Download 48 pages 44.71 Kb
Page 43
Image 43

Service Manual

3Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

120 vac input to the main control board has

• Check 120 vac supply to the transformer.

 

dropped below 80 vac.

 

 

 

• Check wiring connections at the low voltage

Low 24 vac

 

terminal strip.

 

 

 

 

• Check the wire size/length to remote devices.

 

 

• Replace the transformer.

 

 

 

Watch Dog Error

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

Write EEProm

The main control board has detected an

• Replace the main control board.

internal fault.

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

CRC Parameters

internal fault.

 

 

 

 

 

The main control board has detected an

• Replace the main control board.

No Error Stored

internal fault.

 

 

 

 