Chimney Termination Requirements

Stove Installation (for qualified installers only)

13

Chimney Termination Requirements

Must have an approved cap (to prevent water from entering)

Must not be located where it will become plugged by snow or other material

Must terminate at least 3' above the roof and at least 2' above any portion of the roof within 10' (see Figure 8)

Slanted Roofs

Chimney must extend 3' above the roof

Flat

Chimney must extend 3' above the roof

Chimney must extend 2' above any portion of the roof within 10' of the chimney

Chimney must extend 2' above any portion of the roof within 10' of the chimney

Figure 8

Outside Air Requirements

Required for mobile homes and in certain localities (check with building officials)

Must not be drawn from an enclosed space (garage, unventilated crawl space)

Requires 3” aluminum duct (do not use plastic “dryer-vent”) and a hose-clamp for securing to the stove. Maximum 4’ length. NOTE: A 10’ length is allowed if using 4” diameter duct (use a 3” to 4” converter).

If using the optional blower, you may need to “ovalize” the duct to route it under the blower box.

A screen is required to prevent rodents from entering.

3” Air Duct (max. 4’ length)

Air may be drawn from a ventilated crawl space

Outside air entrance must be placed so it does not become blocked by snow.

Botttom of Stove

Use a hose clamp to secure the aluminum air duct to the air inlet flange on the stove.

Air Duct (3” Dia.)

Figure 9

© Travis Industries

100-01177