Interior or Exterior Masonry Chimney

18

Stove Installation (for qualified installers only)

Interior or Exterior Masonry Chimney

NOTE:

This type of installation requires a UBC approved masonry connector or other method approved by the NFPA 211 standard. See Chimney Connector Requirements on page 11 for further details.

NOTE: The chimney must have a clay tile liner. If it does not, the installation must use a positive connection (full reline). The entire fireplace and chimney must be clean, undamaged, and meet all local building codes (UBC, etc.). Damage must be repaired prior to installation. The chimney must be 15' to 33' tall.

See the section "Stove Placement Requirements" for minimum clearances required.

Min. 18" clearance to ceiling

Clay Liner

This type of installation requires a UBC approved masonry connector or other method approved by the NFPA 211 standard.

Chimney connector sections

See the section "Floor Protection Requirements"

Full Re-Line (recommended)

Make sure the clean-out seals in place.

Figure 17