DEFINITY AUDIX System Release 4.0

Issue 1

System Description Pocket Reference 585-300-214

May 1999

 

 

Design and Operation

 

Operating Requirements

2-13

 

 

Table 2-4 shows the system’s atmospheric requirements.

Table 2-4. Atmospheric Requirements

Temperature1 (° F)

Relative humidity (%)

Air pressure (psi)

65 to 85

20 to 60

9.4 to 15.2

 

 

 

 

1.For customer sites at altitudes above 5000 feet, subtract 1°F from the maximum temperature for every 1000 feet over 5000. For example, the maximum temperature at 6000 feet is 84°F; the maximum temperature at 7000 feet is 83°F

Table 2-5 shows the system’s tolerance for airborne contaminants.

Table 2-5. Air Purity Requirements

Contaminant

Average Concentration

 

 

 

Total particulate matter, including the following:

 

 

Dust

 

 

Lint

 

 

Carbon particles

 

 

Paper fiber

 

 

Metal fragments

185.00 microgram/m3

Nitrate in particulate matter

12.00 microgram/m3

 

Corrosive gases

 

 

Total hydrocarbons equivalent to methane

10.00 ppm

Sulphur dioxide

0.20 ppm

Oxides of nitrogen

0.30 ppm

Total oxidants equivalent to ozone

0.05 ppm

Hydrogen sulfide

0.10 ppm

 

 

 

Page 29
Image 29
Lucent Technologies Release 4.0 manual Atmospheric Requirements, Air Purity Requirements