DEFINITY AUDIX System Release 4.0 | Issue 1 | 
System Description Pocket Reference  | May 1999 | 
  | 
  | 
Design and Operation | 
  | 
Operating Requirements  | |
  | 
  | 
Table 
Table 2-4.  Atmospheric Requirements
Temperature1 (° F)  | Relative humidity (%)  | Air pressure (psi)  | |
65 to 85 | 20 to 60 | 9.4 to 15.2  | |
  | 
  | 
  | 
  | 
1.For customer sites at altitudes above 5000 feet, subtract 1°F from the maximum temperature for every 1000 feet over 5000. For example, the maximum temperature at 6000 feet is 84°F; the maximum temperature at 7000 feet is 83°F
Table 
Table 2-5.  Air Purity Requirements
Contaminant | Average Concentration | |
  | 
  | 
  | 
Total particulate matter, including the following:  | 
  | 
  | 
Dust  | 
  | 
  | 
Lint  | 
  | 
  | 
Carbon particles  | 
  | 
  | 
Paper fiber  | 
  | 
  | 
Metal fragments  | 185.00 microgram/m3  | |
Nitrate in particulate matter  | 12.00 microgram/m3  | 
  | 
Corrosive gases  | 
  | 
  | 
Total hydrocarbons equivalent to methane  | 10.00 ppm  | |
Sulphur dioxide  | 0.20 ppm  | |
Oxides of nitrogen  | 0.30 ppm  | |
Total oxidants equivalent to ozone  | 0.05 ppm  | |
Hydrogen sulfide  | 0.10 ppm  | |
  | 
  | 
  |