Section 3 | Operation |
|
|
WATER LEVEL CHECK
Check the water level while the ice machine is in the ice mode and the water pump is running. The correct water level is 1/4”(6.3mm) to 3/8” (9.5mm) below the top of the standpipe a line in the water trough indicates the correct level.
SIPHON CAP
ICE BRIDGE THICKNESS CHECK
The ice thickness probe is
1.Inspect the bridge connecting the cubes. It should be about 1/8” (3.2 mm) thick.
2.If adjustment is necessary, turn the ice thickness probe adjustment screw clockwise to increase bridge thickness, or counterclockwise to decrease bridge thickness.
NOTE: Turning the adjustment 1/3 of a turn will change the ice thickness about 1/16” (1.5 mm).
ADJUSTING SCREW
SET THE WATER LEVEL
TO THE LINE IN THE
WATER TROUGH
Water Level
The float valve is
1.Verify the ice machine is level (see page
2.Remove the siphon cap from the standpipe.
3.Place the main ON/OFF/WASH toggle switch to the ON position, and wait until the float valve stops adding water.
4.Adjust the water level to (1/4" to 3/8" (6.3 to 9.5 mm) below the standpipe) the line in the water trough:
5.Loosen the two screws on the float valve bracket.
6.Raise or lower the float valve assembly as necessary, then tighten the screws.
7.Move the main ON/OFF/ WASH toggle switch to the OFF position. The water level in the trough will rise above the standpipe and run down the drain.
8.Replace the siphon cap on the standpipe, and verify water level and siphon action by repeating steps 3 through 5.
1/8” ICE BRIDGE THICKNESS
Ice Thickness Check
Make sure the ice thickness probe wire and the bracket do not restrict movement of the probe.
Part Number 000001130 12/08 |