Maintenance | Section 4 |
|
|
C.Remove the Ice Thickness Probe
•Compress the side of the ice thickness probe near the top hinge pin and remove it from the bracket.
ICE THICKNESS
PROBE
COMPRESS SIDES OF ICE
THICKNESS PROBE
Ice Thickness Probe Removal
NOTE: At this point, the ice thickness probe can easily be cleaned. If complete removal is desired follow the ice thickness probe wire to the bulkhead grommet (exit point) in the back wall. Pop the bulkhead grommet out of the back wall by inserting fingernails or a flat object between the back wall and the grommet and prying forward. Pull the bulkhead grommet and wire forward until the connector is accessible, then disconnect the wire lead from the connector.
Ice Thickness Probe Cleaning
•Mix a solution of Manitowoc ice machine cleaner and water (2 ounces of cleaner to 16 ounces of water) in a container.
•Soak the ice thickness probe a minimum of 10 minutes.
Clean all ice thickness probe surfaces and verify the ice thickness probe cavity is clean. Rinse thoroughly with clean water, then dry completely. Incomplete rinsing and drying of the ice thickness probe can cause premature harvest.
D.Remove the Water Distribution Tube Q210/Q270 Models
1. LIFT UP | 3 | 2 |
| ||
2. SLIDE BACK |
| 1 |
3. SLIDE TO RIGHT
DISTRIBUTION
TUBE
THUMBSCREW
LOCATING
PIN
THUMBSCREW
Q210/Q270 Water Distribution Tube Removal
•Loosen the two thumbscrews, which secure the distribution tube.
•Lift the right side of the distribution tube up off the locating pin, then slide it back and to the right.
!Caution
Do not force this removal. Be sure the locating pin is clear of the hole before sliding the distribution tube out.
Disassembly
•Twist both of the inner tube ends until the tabs line up with the keyways.
•Pull the inner tube ends outward.
INNER TUBE
INNER TUBE | TAB |
|
KEYWAY
Q210/Q270 Water Distribution Tube Disassembly
Part Number 000001130 12/08 |