Section 2

Installation Instructions

 

 

CALCULATING REMOTE CONDENSER

INSTALLATION DISTANCES

Line Set Length

The maximum length is 100' (30.5 m).

The ice machine compressor must have the proper oil return. The receiver is designed to hold a charge sufficient to operate the ice machine in ambient temperatures between -20°F (-29°C) and 120°F (49°C), with line set lengths of up to 100' (30.5 m).

Line Set Rise/Drop

The maximum rise is 35' (10.7 m).

The maximum drop is 15' (4.5 m).

!Caution

If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.

Calculated Line Set Distance

The maximum calculated distance is 150' (45.7 m).

Line set rises, drops, horizontal runs (or combinations of these) in excess of the stated maximums will exceed compressor start-up and design limits. This will cause poor oil return to the compressor.

Make the following calculations to make sure the line set layout is within specifications.

1.Insert the measured rise into the formula below. Multiply by 1.7 to get the calculated rise. (Example: A condenser located 10 feet above the ice machine has a calculated rise of 17 feet.)

2.Insert the measured drop into the formula below. Multiply by 6.6 to get the calculated drop. (Example. A condenser located 10 feet below the ice machine has a calculated drop of 66 feet.)

3.Insert the measured horizontal distance into the formula below. No calculation is necessary.

4.Add together the calculated rise, calculated drop, and horizontal distance to get the total calculated distance. If this total exceeds 150' (45.7 m), move the condenser to a new location and perform the calculations again.

Maximum Line Set Distance Formula

Step 1.

Measured Rise (35' [10.7 m] Maximum)

 

 

______ x 1.7

=

_______ Calculated Rise

Step 2.

Measured Drop (15' [4.5 m] Maximum)

 

 

______ x 6.6

=

_______ Calculated Drop

Step 3.

Measured Horizontal Distance (100' [30.5 m] Maximum)

 

_______

 

Horizontal Distance

Step 4.

Total Calculated Distance 150' (45.7 m)

 

 

 

 

 

 

 

_______

 

Total Calculated Distance

 

 

H

 

 

 

 

 

 

H

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV1196

 

 

 

 

 

SV1195

 

 

 

 

 

 

 

SV1194

Combination of a Rise and a

Combination of a Drop and a

 

Combination of a Rise, a Drop

 

Horizontal Run

 

 

Horizontal Run

 

and a Horizontal Run

Part Number 80-1620-3

2-17

Page 29
Image 29
Manitowoc Ice S manual Calculating Remote Condenser Installation Distances