Installation Instructions | Section 2 |
|
|
WATER SUPPLY AND DRAIN LINE SIZING/CONNECTIONS
!Caution
Plumbing must conform to state and local codes.
Location | Water Temperature | Water Pressure | Ice Machine Fitting | Tubing Size Up to Ice | |
Machine Fitting | |||||
|
|
|
| ||
Ice Making | 35°F (1.6°C) Min. | 20 psi (137.9 kPA) Min. | 3/8" Female Pipe | 3/8" (.95 cm) minimum | |
Water Inlet | 90°F (32.2°C) Max. | 80 psi (551.5 kPA) Max. | Thread | inside diameter | |
Ice Making | 1/2" Female | 1/2" (1.27 cm) minimum | |||
Water Drain | Pipe Thread | inside diameter | |||
|
| ||||
Condenser | 40°F (4.4°C) Min. | 20 psi (137.9 kPA) Min. | 3/8" Female Pipe Thread | ||
Water Inlet | 90°F (32.2°C) Max. | 150 psi (1034.2 kPA) Max. | |||
|
| ||||
Condenser | 1/2" Female | 1/2" (1.27 cm) minimum | |||
Water Drain | Pipe Thread | inside diameter | |||
|
| ||||
Bin Drain | 3/4" Female | 3/4" (1.91 cm) minimum | |||
Pipe Thread | inside diameter | ||||
|
|
|
Refer to “Ice Machine Dimensions” at the beginning of Section 2 for the exact locations of inlets and drains for the model you are working on.
ELECTRICAL ENTRANCE |
18” (46 CM) VENT TUBE |
1/2” DRAIN CONNECTION |
PLASTIC FITTING ON OPPOSITE |
SIDE DO NOT APPLY HEAT |
1/2” (1.3 CM) MIN DRAIN ID
AIR GAP
OPEN, TRAPPED AND
VENTED DRAIN
3/8” FPT ICE MAKING WATER INLET FITTING, PLASTIC FITTING ON OPPOSITE SIDE DO NOT APPLY HEAT
3/8” FPT CONDENSER WATER INLET (WATER COOLED UNITS ONLY
1/2” FPT CONDENSER WATER DRAIN
(WATER COOLED UNITS ONLY)
1/2” CPVC SOCKET AUXILLARY BASE
DRAIN
DO NOT TRAP DRAIN LINE, |
|
LEAVE AIR GAP BETWEEN | SV3142 |
DRAIN TUBE AND DRAIN |
Typical Water Supply Drain Installation
Part Number |