Manitowoc Ice manual Section Installation Instructions Location of Ice Machine

Models: S

1 56
Download 56 pages 31.88 Kb
Page 19
Image 19

Section 2

Installation Instructions

 

 

Location of Ice Machine

The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.

The location must be free of airborne and other contaminants.

The air temperature must be at least 35°F (1.6°C), but must not exceed 110°F (43.4°C).

Remote air cooled - The air temperature must be at least -20°F (-29°C), but must not exceed 120°F (49°C)

The location must not be near heat-generating equipment or in direct sunlight and must be protected from weather.

The location must not obstruct air flow through or around the ice machine. Refer to the chart below for clearance requirements.

S300/S320/ S450/S500/

Self-Contained

Water-Cooled

S600/S850/S1000

Air-Cooled

and Remote*

Top/Sides

8" (20.3 cm)

8" (20.3 cm)

Back

5" (12.7 cm)

5" (12.7 cm)

 

 

 

S420

Self-Contained

Water-Cooled

Air-Cooled

and Remote*

 

Top/Sides

12" (30.5 cm)

8" (20.3 cm)

Back

5" (12.7 cm)

5" (12.7 cm)

 

 

 

S1200

Self-Contained

Water-Cooled

Air-Cooled

and Remote*

 

Top

8" (20.3 cm)

8" (20.3 cm)

Sides

12" (30.5 cm)

8" (20.3 cm)

Back

5" (12.7 cm)

5" (12.7 cm)

 

 

 

S1400/S1600/S1800

Self-Contained

Water-Cooled

Air-Cooled

and Remote*

 

Top/Sides

24" (61.0 cm)

8" (20.3 cm)

Back

12" (30.5 cm)

5" (12.7 cm)

*There is no minimum clearance required for water-cooled or remote ice machines. This value is recommended for efficient operation and servicing only.

!Caution

The ice machine must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by exposure to freezing temperatures is not covered by the warranty. See “Removal from Service/Winterization”.

Ice Machine Heat of Rejection

Series

Heat of Rejection

Ice Machine

Air Conditioning

Peak

S300

3800

6000

S320

3800

6000

S420

7000

9600

S450

7000

9600

S500

7000

9600

S600

9000

13900

S850

12000

18000

S1000

16000

22000

S1200

Not Available at

Time of Printing

S1400

19000

28000

S1600

Not Available at

Time of Printing

S1800

24000

36000

B.T.U./Hour

Because the heat of rejection varies during the ice making cycle, the figure shown is an average.

Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment where self-contained air- cooled ice machines are installed.

This information is also necessary when evaluating the benefits of using water-cooled or remote condensers to reduce air conditioning loads. The amount of heat added to an air conditioned environment by an ice machine using a water-cooled or remote condenser is negligible.

Knowing the amount of heat rejected is also important when sizing a cooling tower for a water-cooled condenser. Use the peak figure for sizing the cooling tower.

Part Number 80-1620-3

2-7

Page 19
Image 19
Manitowoc Ice manual Section Installation Instructions Location of Ice Machine, Ice Machine Heat of Rejection