7.4.4.3 Measurements table

 

Description of the physical quantity

Word (hex)

Unit

 

 

 

 

 

 

 

 

I1 (I phase 1) mains 1

 

100

A

 

 

I2 (I phase 2) mains 1

 

101

A

 

I3 (I phase 3) mains 1

 

102

A

 

I1 (I phase 1) mains 2

 

106

A

 

I2 (I phase 2) mains 2

 

107

A

 

I3 (I phase 3) mains 2

 

108

A

 

I1 (I phase 1) output

 

109

A

 

I2 (I phase 2) output

 

10A

A

 

I3 (I phase 3) output

 

10B

A

 

I battery

 

10E

A

 

U12 mains 1

 

115

V

 

U23 mains 1

 

116

V

 

U31 mains 1

 

117

V

 

U mains 2 (phase 1)

 

11E

V

 

U mains 2 (phase 2)

 

11F

V

 

U mains 2 (phase 3)

 

120

V

 

U12 mains 2

 

121

V

 

U23 mains 2

 

122

V

 

U31 mains 2

 

123

V

 

U1N output

 

124

V

 

U2N output

 

125

V

 

U3N output

 

126

V

 

U12 output

 

127

V

 

U23 output

 

128

V

 

U31 output

 

129

V

 

U battery

 

12D

V

 

Output active power (phase 1)

130

W

 

Output active power (phase 2)

131

W

 

Output active power (phase 3)

132

W

 

Output apparent power (phase 1)

133

VA

 

Output apparent power (phase 2)

134

VA

 

Output apparent power (phase 3)

135

VA

 

Output total active power

 

136

W

 

Output total apparent power

 

137

VA

 

% output load level

 

139

%

 

 

Peak factor phase 1 x 100

 

13A

-

 

 

Peak factor phase 2 x 100

 

13B

-

 

 

Peak factor phase 3 x 100

 

13C

-

 

 

Power factor x 100

 

13D

-

 

 

Mains 1 frequency

 

13E

dHz

 

Mains 2 frequency

 

140

dHz

 

Output frequency

 

141

dHz

 

Battery backup time

 

149

Min

 

Battery charging level

 

14B

%

 

 

 

 

 

 

 