7.4.4.2 Modular fault table
Description du Status | Status to 0 | Status to 1 | Word | Bit | |
|
|
|
| (hex) |
|
|
|
|
|
|
|
Module 1 | General alarm | Absent | Present | 61 | 0 |
| Fan failure | Absent | Present | 61 | 1 |
| Internal communication fault | Absent | Present | 61 | 2 |
| Inverter thermal overload | Absent | Present | 61 | 3 |
| Inverter fault | Absent | Present | 61 | 4 |
| Inverter fuse blown | Absent | Present | 61 | 5 |
| Load short circuit | Absent | Present | 61 | 6 |
Module 2 | General alarm | Absent | Present | 62 | 0 |
| Fan failure | Absent | Present | 62 | 1 |
| Internal communication fault | Absent | Present | 62 | 2 |
| Inverter thermal overload | Absent | Present | 62 | 3 |
| Inverter fault | Absent | Present | 62 | 4 |
| Inverter fuse blown | Absent | Present | 62 | 5 |
| Load short circuit | Absent | Present | 62 | 6 |
Module 3 | General alarm | Absent | Present | 63 | 0 |
| Fan failure | Absent | Present | 63 | 1 |
| Internal communication fault | Absent | Present | 63 | 2 |
| Inverter thermal overload | Absent | Present | 63 | 3 |
| Inverter fault | Absent | Present | 63 | 4 |
| Inverter fuse blown | Absent | Present | 63 | 5 |
| Load short circuit | Absent | Present | 63 | 6 |
Module 4 | General alarm | Absent | Present | 64 | 0 |
| Fan failure | Absent | Present | 64 | 1 |
| Internal communication fault | Absent | Present | 64 | 2 |
| Inverter thermal overload | Absent | Present | 64 | 3 |
| Inverter fault | Absent | Present | 64 | 4 |
| Inverter fuse blown | Absent | Present | 64 | 5 |
| Load short circuit | Absent | Present | 64 | 6 |
|
|
|
|
|
|
|
|
|
|
|
|
ENERGIZE YOUR ENTERPRISE |
|
|