7.4JBUS table
7.4.1 Data for Pulsar 700 / 1000 / 1500
7.4.1.1 Status table
Status description | Status to 0 | Status to 1 | Word (hex) | Bit | |
|
|
|
|
| |
Load protected | no | yes | 40 | 0 | |
UPS coupled | no | yes | 40 | 1 | |
Unit general alarm | no | yes | 40 | 2 | |
UPS in backup | no | yes | 40 | 4 | |
Battery low warning | no | yes | 40 | 5 | |
Low battery | no | yes | 40 | 6 | |
Operation on static switch | no | yes | 40 | 7 | |
Communication fault | absent | present | 40 | 9 | |
UPS overload | no | yes | 40 | A | |
Emergency stop | absent | present | 40 | B | |
Battery to be checked | no | yes | 40 | D | |
Device ventilation fault | no | yes | 40 | E | |
Battery present | absent | present | 42 | 0 | |
Mains 1 voltage out of tolerance | no | yes | 44 | 8 | |
Mains 1 frequency out of tolerance | no | yes | 44 | B | |
Bypass status | no | yes | 46 | 7 | |
Charger general fault | no | yes | 49 | 0 | |
Battery charge | not in | in charge | 49 | 1 & 3 | |
charge | |||||
|
|
|
| ||
Converter fault | no | yes | 4A | 1 | |
Inverter fault | no | yes | 4C | 1 | |
|
|
|
|
|