3 Configuration

3.1Configure IP parameters

Once the card has started:

Connect one end of the cable (34003918) to the Service port.

If the environment sensor was previously connected, the card must be restarted in order to access the configuration menu.

Connect the other end of the cable to the COM port (IOIOI) of a PC.

Launch a HyperTerminal™ type emulator with the foll owing configuration:

Speed: 9600

Data bits: 8

Parity: none

Stop bits: 1

Flow control: none

"Locally reproduce the characters entered" option: deactivated.

Enter MGEUPS or mgeups. The main menu is displayed:

-----------------------------------------------------------------------------

MGE UPS SYSTEMS

NETWORK MANAGEMENT CARD

-----------------------------------------------------------------------------

1 : Reset

2 : Network configuration

3 : Set Login Password to Default

4 : Return to Default Configuration

0 : Exit

-----------------------------------------------------------------------------

ENERGIZE YOUR ENTERPRISE

 

 

Network Management Card – User Manual

34003991EN/DA

Page 17/120

Page 17
Image 17