7.4.2 Data for Pulsar M 2200 / 3000

7.4.2.1 Status table

 

Status description

 

Status to 0

 

Status to 1

 

Word (hex)

Bit

 

 

 

 

 

 

 

 

 

 

 

 

Load protected

 

no

 

yes

40

0

 

 

UPS coupled

 

no

 

yes

40

1

 

 

Unit general alarm

 

no

 

yes

40

2

 

 

UPS in backup

 

no

 

yes

40

4

 

 

Battery low warning

 

no

 

yes

40

5

 

 

Low battery

 

no

 

yes

40

6

 

 

Operation on static switch

 

no

 

yes

40

7

 

 

Communication fault

 

absent

 

present

40

9

 

 

UPS overload

 

no

 

yes

40

A

 

Emergency stop

 

absent

 

present

40

B

 

Battery to be checked

 

no

 

yes

40

D

 

Device ventilation fault

 

no

 

yes

40

E

 

Manual bypass switch (Q3BP)

 

open

 

closed

41

6

 

 

Battery present

 

absent

 

present

42

0

 

 

Mains 1 voltage out of tolerance

 

no

 

yes

44

8

 

 

Mains 1 frequency out of tolerance

 

no

 

yes

44

B

 

Redundancy lost

 

no

 

yes

45

7

 

 

Maintenance position

 

no

 

yes

46

1

 

 

Mains 2 overload

 

no

 

yes

46

5

 

 

Output on bypass

 

no

 

yes

46

7

 

 

Mains 2 frequency out of tolerance

 

no

 

yes

46

9

 

 

Mains 2 voltage out of tolerance

 

no

 

yes

46

A

 

Phase M2 out of tolerance

 

no

 

yes

46

B

 

Charger general fault

 

no

 

yes

49

0

 

 

Battery charge

 

no

 

yes

49

1 & 3

 

 

Converter fault

 

no

 

yes

 

4A

1

 

 

 

 

 

 

 

Inverter major fault

 

no

 

yes

 

4C

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 