8.2SNMP objects

8.2.1 MGE MIB

The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed. The entire MIB description is available on www.mgeops.com area “ Downloads – Software Download . Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705. 1.

MIB object

SNMP Format

Add.path

 

 

 

 

 

 

upsmgIdentFamilyName

String

 

{1,1,0}

 

 

 

 

 

 

upsmgIdentModelName

String

 

{1,2,0}

 

 

 

 

 

 

upsmgIdentFirmwareVersion

String

 

{1,4,0}

 

 

 

 

 

 

upsmgIdentSerialNumber

String

 

{1,7,0}

 

 

 

 

 

 

upsmgConfigLowBatteryTime

seconds

 

{4,7,0}

 

 

 

 

 

 

upsmgConfigLowBatteryLevel

%

 

{4,8,0}

 

 

 

 

 

 

upsmgConfigAutoRestart

1(yes) 2(no)

 

{4,9,0}

 

 

 

 

 

 

upsmgConfigVARating

VA

 

{4,12,0}

 

 

 

 

 

 

upsmgBatteryRemainingTime

seconds

 

{5,1,0}

 

 

 

 

 

 

upsmgBatteryLevel

%

 

{5,2,0}

 

 

 

 

 

 

upsmgBatteryVoltage

deciVolts

 

{5,5,0}

 

 

 

 

 

 

upsmgBatteryCurrent

deciAmps

 

{5,6,0}

 

 

 

 

 

 

upsmgBatteryFaultBattery

1(yes) 2(no)

 

{5,9,0}

 

 

 

 

 

 

upsmgBatteryReplacement

1(yes) 2(no)

 

{5,11,0}

 

 

 

 

 

 

upsmgBatteryLowBattery

1(yes) 2(no)

 

{5,14,0}

 

 

 

 

 

 

upsmgBatteryChargerFault

1(yes) 2(no)

 

{5,15,0}

 

 

 

 

 

 

upsmgBatteryLowCondition

1(yes) 2(no)

 

{5,16,0}

 

 

 

 

 

 

upsmgInputPhaseNum

 

 

{6,1,0}

 

 

 

 

 

 

mginputVoltage_1

DeciVolts

 

{6,2,1,2,1,0}

 

 

 

 

 

 

mginputVoltage_2

DeciVolts

 

{6,2,1,2,2,0}

 

 

 

 

 

 

mginputVoltage_3

DeciVolts

 

{6,2,1,2,3,0}

 

 

 

 

 

 

mginputFrequency_1

DeciHz

 

{6,2,1,3,1,0}

 

 

 

 

 

 

mginputFrequency_2

DeciHz

 

{6,2,1,3,2,0}

 

 

 

 

 

 

mginputFrequency_3

DeciHz

 

{6,2,1,3,3,0}

 

 

 

 

 

 

mginputMinimumVoltage

 

 

{6,2,1,4,0}

 

 

 

 

 

 

mginputMaximumVoltage

 

 

{6,2,1,5,0}

 

 

 

 

 

 

mginputCurrent_1

DeciAmps

 

{6,2,1,6,1,0}

 

 

 

 

 

 

mginputCurrent_2

DeciAmps

 

{6,2,1,6,2,0}

 

 

 

 

 

 

mginputCurrent_3

DeciAmps

 

{6,2,1,6,3,0}

 

 

 

 

 

 

upsmgInputBadStatus

 

 

{6,3,0}

 

 

 

 

 

 

upsmgInputLineFailCause

 

 

{6,4,0}

 

 

 

 

 

 

upsmgOutputPhaseNum

 

 

{7,1,0}

 

 

 

 

 

 

mgoutputPhaseIndex_1

 

 

{7,2,1,1,1,0}

 

 

 

 

 

 

mgoutputPhaseIndex_2

 

 

{7,2,1,1,2,0}

 

 

 

 

 

 

mgoutputPhaseIndex_3

 

 

{7,2,1,1,3,0}

 

 

 

 

 

 

mgoutputVoltage_1

deciVolts

 

{7,2,1,2,1,0}

 

 

 

 

 

 

mgoutputVoltage_2

deciVolts

 

{7,2,1,2,2,0}

 

 

 

 

 

 

mgoutputVoltage_3

deciVolts

 

{7,2,1,2,3,0}

 

 

 

 

 

 

ENERGIZE YOUR ENTERPRISE

 

 

 

 

Network Management Card – User Manual

34003991EN/DA

Page 112/120

Page 112
Image 112
MGE UPS Systems 66103, 66102 user manual Snmp objects, Mge Mib