MGE UPS Systems 66103, 66102 user manual Snmp objects, Mge Mib

Models: 66102 66103

1 120
Download 120 pages 20.59 Kb
Page 112
Image 112

8.2SNMP objects

8.2.1 MGE MIB

The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed. The entire MIB description is available on www.mgeops.com area “ Downloads – Software Download . Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705. 1.

MIB object

SNMP Format

Add.path

 

 

 

 

 

 

upsmgIdentFamilyName

String

 

{1,1,0}

 

 

 

 

 

 

upsmgIdentModelName

String

 

{1,2,0}

 

 

 

 

 

 

upsmgIdentFirmwareVersion

String

 

{1,4,0}

 

 

 

 

 

 

upsmgIdentSerialNumber

String

 

{1,7,0}

 

 

 

 

 

 

upsmgConfigLowBatteryTime

seconds

 

{4,7,0}

 

 

 

 

 

 

upsmgConfigLowBatteryLevel

%

 

{4,8,0}

 

 

 

 

 

 

upsmgConfigAutoRestart

1(yes) 2(no)

 

{4,9,0}

 

 

 

 

 

 

upsmgConfigVARating

VA

 

{4,12,0}

 

 

 

 

 

 

upsmgBatteryRemainingTime

seconds

 

{5,1,0}

 

 

 

 

 

 

upsmgBatteryLevel

%

 

{5,2,0}

 

 

 

 

 

 

upsmgBatteryVoltage

deciVolts

 

{5,5,0}

 

 

 

 

 

 

upsmgBatteryCurrent

deciAmps

 

{5,6,0}

 

 

 

 

 

 

upsmgBatteryFaultBattery

1(yes) 2(no)

 

{5,9,0}

 

 

 

 

 

 

upsmgBatteryReplacement

1(yes) 2(no)

 

{5,11,0}

 

 

 

 

 

 

upsmgBatteryLowBattery

1(yes) 2(no)

 

{5,14,0}

 

 

 

 

 

 

upsmgBatteryChargerFault

1(yes) 2(no)

 

{5,15,0}

 

 

 

 

 

 

upsmgBatteryLowCondition

1(yes) 2(no)

 

{5,16,0}

 

 

 

 

 

 

upsmgInputPhaseNum

 

 

{6,1,0}

 

 

 

 

 

 

mginputVoltage_1

DeciVolts

 

{6,2,1,2,1,0}

 

 

 

 

 

 

mginputVoltage_2

DeciVolts

 

{6,2,1,2,2,0}

 

 

 

 

 

 

mginputVoltage_3

DeciVolts

 

{6,2,1,2,3,0}

 

 

 

 

 

 

mginputFrequency_1

DeciHz

 

{6,2,1,3,1,0}

 

 

 

 

 

 

mginputFrequency_2

DeciHz

 

{6,2,1,3,2,0}

 

 

 

 

 

 

mginputFrequency_3

DeciHz

 

{6,2,1,3,3,0}

 

 

 

 

 

 

mginputMinimumVoltage

 

 

{6,2,1,4,0}

 

 

 

 

 

 

mginputMaximumVoltage

 

 

{6,2,1,5,0}

 

 

 

 

 

 

mginputCurrent_1

DeciAmps

 

{6,2,1,6,1,0}

 

 

 

 

 

 

mginputCurrent_2

DeciAmps

 

{6,2,1,6,2,0}

 

 

 

 

 

 

mginputCurrent_3

DeciAmps

 

{6,2,1,6,3,0}

 

 

 

 

 

 

upsmgInputBadStatus

 

 

{6,3,0}

 

 

 

 

 

 

upsmgInputLineFailCause

 

 

{6,4,0}

 

 

 

 

 

 

upsmgOutputPhaseNum

 

 

{7,1,0}

 

 

 

 

 

 

mgoutputPhaseIndex_1

 

 

{7,2,1,1,1,0}

 

 

 

 

 

 

mgoutputPhaseIndex_2

 

 

{7,2,1,1,2,0}

 

 

 

 

 

 

mgoutputPhaseIndex_3

 

 

{7,2,1,1,3,0}

 

 

 

 

 

 

mgoutputVoltage_1

deciVolts

 

{7,2,1,2,1,0}

 

 

 

 

 

 

mgoutputVoltage_2

deciVolts

 

{7,2,1,2,2,0}

 

 

 

 

 

 

mgoutputVoltage_3

deciVolts

 

{7,2,1,2,3,0}

 

 

 

 

 

 

ENERGIZE YOUR ENTERPRISE

 

 

 

 

Network Management Card – User Manual

34003991EN/DA

Page 112/120

Page 112
Image 112
MGE UPS Systems 66103, 66102 user manual Snmp objects, Mge Mib