| 4. Advanced Operations | |
| Environmental Monitor Status traps | |||
| Status | Error | Description | |
|
|
|
| |
| Normal |
| The Environmental Monitor is working correctly | |
|
|
|
| |
| NoComm | x | Communication to the Environmental Monitor has been lost | |
Temperature/Humidity Sensor Status traps | ||||
| Status | Error | Description | |
|
|
|
| |
| Found |
| The sensor has been detected | |
|
|
|
| |
| NotFound |
| No sensor has been detected | |
|
|
|
| |
| Lost | x | Sensor initially detected but communication to the sensor has been lost | |
|
|
|
| |
| NoComm | x | Communication to the sensor has been lost |
NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal.
Change trapThe Change trap is generated for all outlet status changes between any on/off conditions. Change traps include the outlet status, Location of the AmpMeter PDU, and identifier and name of the affected outlet. For descriptions of the outlet status types, please refer to the prior table.
Load TrapThe Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps include the reported input load, load status, Location of the AmpMeter PDU, and identifier and name of the affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Load returns to a
Load traps
Status | Error | Description |
Normal |
| Infeed is on and within preset thresholds |
|
|
|
NotOn |
| Infeed is off |
|
|
|
Reading |
| |
|
|
|
LoadHigh | x | Infeed current load exceeds preset threshold |
|
|
|
OverLoad | x | Infeed current load exceeds the measurable range for the infeed |
|
|
|
ReadError | x | Unable to read Load status |
|
|
|
NoComm | x | Communication to the infeed has been lost |