Miele DA 3590 EXT, DA 3560 EXT installation instructions Connection for air extraction

Models: DA 3560 EXT DA 3560 DA 3590 EXT DA 3590

1 44
Download 44 pages 12.77 Kb
Page 38
Image 38
Connection for air extraction

Connection for air extraction

Important: To avoid the danger of toxic fumes, please observe the Warning and Safety instructions. This is especially crucial when using the cooker hood at the same time as another heating appliance which relies on air from the same room. The cooker hood should be installed according to local and national building regulations. Seek approval from the building inspector where necessary.

Only use smooth pipes or flexible hoses made from non-flammable materials for the extraction ducting.

When using an external motor, make sure that the exhaust ducting is sufficiently rigid. The external motor can cause an underpressure which can result in the exhaust ducting distorting.

To achieve the greatest possible air extraction with the lowest noise level, please note the following:

To ensure efficient air extraction, the diameter of the exhaust ducting should not be less than 150 mm.

If flat ducting is being used, the cross-section must not be smaller than the cross-section of the exhaust connection.

All ducting, pipework and fittings must be of non-flammable materials.

The exhaust ducting should be as short and straight as possible.

Only use wide radius bends.

The exhaust ducting should not be kinked or compressed.

Ensure that all connections are strong and airtight.

Where ducting is horizontal, it must be laid to slope away at at least 1 cm per metre. This is to ensure that condensate cannot drain back into the cooker hood.

38

Page 38
Image 38
Miele DA 3590 EXT, DA 3560 EXT installation instructions Connection for air extraction