SECTION 6 – OPERATING AUXILIARY EQUIPMENT

6-1. 120 Volt Duplex And Optional GFCI Receptacles

4

Y If unit does not have GFCI re- ceptacles, use GFCI-pro- tected extension cord.

1 120 V 15 A AC Receptacle RC1

2 120 V 15 A AC Receptacle RC2

 

 

 

 

 

 

 

 

3 120 V 15 A AC GFCI Recep-

1

 

 

2

 

 

tacles GFCI1 And GFCI2

 

 

 

 

(Optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Receptacles supply 60 Hz single-

 

 

 

 

 

 

 

 

phase power at weld/power speed.

 

 

 

 

 

 

 

5

4

Circuit Breaker CB1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Circuit Breaker CB2

 

 

 

 

 

 

 

 

CB1 protects RC1/GFCI1 and CB2

 

 

 

 

 

 

 

 

protects RC2/GFCI2 from over-

 

 

 

 

 

 

 

 

load. If CB1 or CB2 opens, the re-

 

 

 

 

 

 

 

 

ceptacle does not work. Press but-

 

 

 

 

 

 

 

 

ton to reset circuit breaker.

 

 

 

 

 

 

 

 

. If a circuit breaker continues to

 

 

 

 

 

 

 

 

 

open,

contact

a Factory

 

 

 

 

 

 

 

 

 

Authorized Service Agent.

 

 

 

 

 

 

 

 

If a ground fault is detected, the

 

 

 

 

 

 

 

 

GFCI Reset button pops out and

 

 

 

 

 

 

 

 

the circuit opens to disconnect the

 

 

 

 

 

 

 

 

faulty equipment. Check for dam-

 

 

 

 

 

 

 

 

aged tools, cords, plugs, etc. con-

 

 

 

 

 

 

 

 

nected to the receptacle. Press but-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ton to reset receptacle and resume

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

. At least once a month, run en-

 

 

 

 

 

 

 

 

 

gine at weld/power speed and

 

 

 

 

 

 

 

 

 

press Test button to verify

 

 

 

 

 

 

 

 

 

GFCI is working properly.

 

 

 

 

 

 

 

 

Maximum output from each duplex

 

 

 

 

 

 

 

 

receptacle is 1.8 kVA/kW, and 3

 

 

 

 

 

 

 

 

kVA/kW

from all

receptacles.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auxiliary power is not affected by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

weld output.

 

EXAMPLE: If 15 A is drawn from

RC1, only 10 A is available at RC2:

(120 V x 15 A) + (120 V x 10 A) = 3.0 kVA/kW

3

Ref. ST-191 898

OM-477 Page 21

Page 25
Image 25