6-2. 240 Volt Duplex Receptacle (Optional)
Y If unit does not have GFCI re- ceptacles, use
1 240 V 15 A AC Receptacle RC1
Receptacle supplies 60 Hz single-
1phase power at weld/power speed. Maximum output is 3 kVA/kW.
2 Circuit Breaker CB1
3 Circuit Breaker CB2
CB1 and CB2 protect the recep- tacles from overload. If CB1 or CB2 opens, the 240 V receptacle and half of the 120 V receptacle does not work. 120 volts may still be
23present at the 240 V receptacle. Press button to reset circuit breaker.
. If a circuit breaker continues to
open, contact a Factory Authorized Service Agent.
Combined output of all receptacles is 3 kVA/kW. Auxiliary power is not affected by weld output.
EXAMPLE: If 10 A is drawn from the 240 V receptacle, only 5 A is avail- able at the 120 V receptacle:
(240 V x 10 A) + (120 V x 5 A) = 3.0 kVA/kW
Ref.