3-10. Electrical Service Guide

NOTE

Actual input voltage should not exceed ± 10% of indicated required input voltage. If actual input voltage is outside of this range, output may not be available.

 

50/60 Hz Three Phase

 

 

Input Voltage

400

 

 

Input Amperes At Rated Output

17

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

Time-Delay 2

20

Normal Operating 3

25

Min Input Conductor Size In mm2, 4

2.5

Max Recommended Input Conductor Length In Meters

41

 

 

Min Grounding Conductor Size In mm2, 4

2.5

Reference: 1999 National Electrical Code (NEC)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

3-11. Connecting Input Power

2

L1

L2

L3

Green/Yellow

1

YAlways connect grounding conductor first.

= GND/PE

YAlways connect green/yel- low wire to supply ground- ing terminal, never to a line terminal.

Check input voltage available at site.

1Input And Grounding Conductors

2Line Disconnect Device

Select type and size of overcurrent protection using Section 3-10.

Tools Needed: