INSTALLATION

2.6 Connection of Several Inverters

Factory Automation can be applied to several inverters which share a link system as CC-Link remote device stations and are controlled and monitored by PLC user programs.

 

Master module

FR-E5NC

 

 

FR-E5NC

 

 

Termination

 

 

DA

 

 

 

 

 

DA

 

 

 

 

 

 

 

DA

 

 

Termination

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resistor*

 

 

DB

 

 

 

 

 

DB

 

 

 

 

 

 

 

DB

 

resistor*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DG

 

 

 

 

DG

 

 

 

 

 

 

DG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLD Shielded twisted SLD

Shielded twisted SLD

 

 

 

 

 

 

 

cable

 

 

 

 

 

 

cable

 

 

 

 

 

 

 

 

 

 

FG

 

 

FG

 

 

 

FG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Use the termination resistors supplied with the PLC.

1)Maximum number of units connected to one master station 42 units (when only inverters are connected)

If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied:

{(1 a) + (2 b) + (3 c) + (4 d)} 64

a:Number of units occupying 1 station

b:Number of units occupying 2 stations

c:Number of units occupying 3 stations

d:Number of units occupying 4 stations

{(16 A) + (54 B) + (88 C)}

2304

A: Number of remote I/O stations

64

B: Number of remote device stations

42

C: Number of local stations

26

9