HOW TO CHECK FOR ERROR USING THE LEDS
7.3 Communication Stops During Operation
!Check that the
!Check that the programmable controller program is executing reliably and that the PLC CPU is running.
!Check that data communication has not stopped due to an instantaneous power failure, etc.
|
| LED States |
|
|
|
|
| ||
Master |
| Inverters |
| Cause | Corrective Action | ||||
unit | Station 1 | Station 2 | Station 3 |
|
| ||||
| L. RUN $ | L. RUN " | L. RUN $ | Since the L.RUN LEDs of the | After correcting the repeated | ||||
| SD | * | SD | " | SD | * | station 1 and the | ||
| station numbers of the inverters, | ||||||||
| RD | " | RD | " | RD | " | the station numbers of the inverters set as | switch power on again. | |
| L. ERR $ | L. ERR $ | L. ERR $ | stations 1 and 3 are the same. | |||||
|
| ||||||||
| L. RUN " | L. RUN $ | L. RUN " | Since the L.RUN and SD LEDs of the | After correcting the transmission | ||||
| SD | " | SD | $ | SD | " | on station 2 are off, the transmission speed | ||
| speed setting, switch power on | ||||||||
TIME $ | RD | " | RD | " | RD | " | setting of the | ||
again. | |||||||||
LINE $ | L. ERR $ | L. ERR $ | L. ERR $ | within the setting range (0 to 4). | |||||
| |||||||||
or | L. RUN " | L. RUN " | L. RUN " | Since the L.ERR LED of the | After returning the setting switch of | ||||
TIME " | SD | " | SD | " | SD | " | the | ||
LINE $ | RD | " | RD | " | RD | " | 3 flickers, the setting switch of the | position, power on the inverter | |
| L. ERR $ | L. ERR $ | L. ERR # | station 3 was moved during normal operation. | again. | ||||
|
| ||||||||
| L. RUN $ | L. RUN " | L. RUN " | Since the L.RUN and SD LEDs of the |
| ||||
| SD | $ | SD | " | SD | " | on station 1 are off and its L.ERR LED is on, the | After correcting the setting switch | |
| RD | " | RD | " | RD | " | setting switch setting of the | position of the | |
| L. ERR " | L. ERR $ | L. ERR $ | 1 is outside the range (transmission speed: 5 to | power on again. | ||||
|
|
|
|
|
|
| 9, station number: 65 or more). |
|
51