INVERTER SETTING
3.3 Operation at Alarm Occurrence
Fault Location | Description |
|
| Operation Mode |
| |
| PU operation | External operation | ||||
|
|
| ||||
Inverter alarm | Inverter operation |
| Stop (inverter trip) | Stop (inverter trip) | Stop (inverter trip) | |
Data communication | E5NC | Continued | Continued | Continued | ||
| ||||||
Communication alarm (E5NC) | Inverter operation |
| Continued | Continued | Stop (inverter trip) | |
Data communication | E5NC | Stop | Stop | Stop | ||
|
(1)Inverter alarm
Refer to the inverter manual and remove the cause of the alarm.
(2)Communication alarm
Check the LED states of the
(3) Communication error during
When a communication error occurs, the error message "E.OPT" is displayed .
(4)Inverter reset (Note)
(Refer to page 44 for an inverter reset program example.)
| Resetting Method |
| Operation Mode |
| |
| External operation | PU operation | |||
|
| ||||
| Inverter reset (*1) | Allowed | Disallowed | Disallowed | |
PLC program | Instruction code | ||||
|
|
| |||
| Error reset at inverter fault (RY1A) (*2) | Allowed | Allowed | Allowed | |
Connect terminals | Allowed | Allowed | Allowed | ||
Switch off inverter power | Allowed | Allowed | Allowed |
(*1) Inverter reset can be made any time.
(*2) Reset can be made only when the protective function of the inverter is activated.
15