FUNCTION OVERVIEW

4.2 Setting the Running Frequecy

The following table lists the functions which can be executed from the programmable logic controller in the CC-Link system:

Control Location

Item

 

Operation Mode

 

PU operation

External operation

CC-Link operation

 

 

 

Operation command

Disallowed

Disallowed

Allowed

 

Running frequency setting

Disallowed

Disallowed

Allowed

 

Monitoring

Allowed

Allowed

Allowed

 

Parameter write

Disallowed (*3)

Disallowed (*3)

Allowed (*3)

User program

Parameter read

Allowed

Allowed

Allowed

 

Inverter reset

Disallowed

Disallowed

Allowed (*1)

 

Error reset at inverter fault

Allowed (*1)

Allowed (*1)

Allowed (*1)

 

(RY1A)

 

 

 

 

 

Stop command (*2)

Disallowed

Disallowed

Allowed

Control circuit

Inverter reset terminal

Allowed

Allowed

Allowed

Operation command

Disallowed

Allowed

Allowed (*4)

terminal

Frequency setting

Disallowed

Allowed

Allowed (*4)

 

(*1) At occurrence of a communication error, the inverter cannot be reset from the computer. (For inverter reset, refer to the inverter manual.)

(*2) As set in Pr. 75.

(*3) As set in Pr. 77.

Values can be written to Pr. 4 to Pr. 6, Pr. 22, Pr. 24 to Pr. 27, Pr. 52 to Pr. 56, Pr. 72, Pr. 232 to Pr. 239 during operation.

(For full information, refer to the inverter manual.) (*4) As set in Pr. 338 and Pr. 339

Note 1. The inverter goes into the external operation mode if it is reset from the PLC in the CC-Link operation mode. The setting of "1" in Pr. 340 (link start mode) selects CC-Link operation mode.

20