INVERTER SETTING

(2) Operation mode switching method

Change the operation mode as described below:

Switched by

 

Switched

PC program

 

from PU

 

 

C

External

A

 

 

 

 

 

 

CC-Link

 

 

 

PU operation

operation

 

 

 

 

D

B

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

F

(Switching disallowed)

 

 

 

 

Symbol

Switching Type

 

Switching Method

A

PU operation External operation

 

Operate the external operation key on the PU.

B

External operation

PU operation

 

Operate the PU operation key on the PU.

C

External operation

CC-Link operation

 

By the user program of the PLC.

D

CC-Link operation

External operation

 

By the user program of the PLC.

E

PU operation CC-Link operation

 

Switching disallowed. Allowed if external operation is selected in A

 

and CC-Link operation is then selected in C. (Note 2)

 

 

 

 

F

CC-Link operation

PU operation

 

Switching disallowed. Allowed if external operation is selected in D

 

and PU operation is then selected in B. (Note 2)

 

 

 

 

When "1" is set in Pr. 340 "link start mode selection", the operation mode is CC-Link operation at power on or inverter reset.

Note: 1. When setting "1" in Pr. 340, the initial settings (station number setting, etc.) of the inverter must be made without fail.

2. In the switch-over mode (Pr. 79 = 6), switching in E and F is allowed.