COMMUNICATION SPECIFICATIONS

5.1.2 Input signals (inverter (FR-E5NC) master unit)

The input signals to the master unit are indicated. (Output signals from inverter)

Device

Signal

Description

No.

 

 

RX0

Forward running

OFF : Other than forward running (during stop or reverse rotation)

ON : Forward running

 

 

RX1

Reverse running

OFF : Other than reverse running (during stop or forward rotation)

ON : Reverse running

 

 

RX2

Running (RUN)

On while the inverter is running. (Note)

RX3

Up to frequency (SU)

Switched on when the output frequency reaches the set frequency ± Pr. 41.

RX4

Overload (OL)

Switched on when stall prevention is activated and switched off when stall prevention is

deactivated.

 

 

RX5

Reserved

Reserved for the system.

RX6

Frequency detection (FU)

Switched on when the output frequency reaches set frequency. (Note)

RX7

Alarm (A, B, C)

Switched on when the inverter's protective function is activated to stop the output. (Note)

RX8

 

 

RX9

Reserved

Reserved for the system.

RXA

 

 

RXB

 

 

RXC

Monitoring

Switched on when the monitored value is set to RWr0 by the monitor command (RYC)

switching on. Switched off when the monitor command (RYC) is switched off.

 

 

RXD

Frequency setting command

Switched on when the set frequency is written to the inverter by the frequency setting

(RAM)

command (RYD) switching on. Switched off when the frequency setting command

 

(RYD) is switched off.

 

 

RXE

Frequency setting command

Switched on when the set frequency is written to the inverter by the frequency setting

(E2PROM)

command (RYE) switching on. Switched off when the frequency setting command

 

(RYE) is switched off.

 

 

 

Instruction code execution

Switched on on completion of the processing corresponding to the instruction code

RXF

(RWW2) which is executed when the instruction code execution request (RYF) switches

completion

 

on. Switched off when the instruction code execution completion (RXF) is switched off.

 

 