3. Outdoor unit failure mode table

MUZ-GB50VA

The left lamp of

Abnormal point

LED indication

Condition

Correspondence

Indoor/outdoor

OPERATION INDICATOR

(Outdoor P.C. board)

unit failure mode

(Failure mode / protection)

lamp (Indoor unit)

LED 1

LED 2

 

 

 

 

 

 

recall function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

None (Normal)

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-time flash

Outdoor power system

Lighting

Lighting

When over current protection stop is

• Check the connection

 

 

 

 

 

 

 

 

 

continuously performed three times

of the compressor

 

 

 

 

 

 

 

 

 

within 1 minute after the compressor

connecting wire.

 

 

 

 

 

 

 

 

 

gets started, or when converter

• Refer to 10-6.A

 

 

 

 

 

 

 

 

 

protection stop or bus-bar voltage

"How to check

 

 

 

 

 

 

 

 

 

protection stop is continuously

inverter / compressor".

 

 

 

 

 

 

 

 

 

performed three times within 3

• Check the stop valve.

 

 

 

 

 

 

 

 

 

minutes after start-up.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-time flash

Discharge temperature

Lighting

Once

When thermistor shorts or opens

• Refer to 10-6.B"Check

 

 

 

 

 

 

thermistor

 

 

during compressor running.

of outdoor thermistors".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost thermistor

Lighting

Once

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature thermistor

Lighting

Twice

 

 

 

 

 

 

 

 

 

 

 

 

Fin temperature thermistor

Lighting

3 times

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board temperature

Lighting

4 times

 

 

 

• Replace the outdoor

 

 

 

 

 

 

thermistor

 

 

 

 

 

electronic control

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

Outdoor heat exchanger

Lighting

9 times

 

 

 

• Refer to 10-6.B"Check

 

 

 

 

 

 

temperature thermistor

 

 

 

 

 

of outdoor thermistors".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-time flash

Over current

Once

Goes

When 28A current flow into intelligent

• Reconnect compressor

 

 

 

 

 

 

 

 

out

power module.

connector.

 

 

 

 

 

 

 

 

 

 

 

 

• Refer to 10-6.A"How to

 

 

 

 

 

 

 

 

 

 

 

 

check inverter/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor."

 

 

 

 

 

 

 

 

 

 

 

 

• Check the stop valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-time flash

Discharge temperature

Lighting

Lighting

When discharge temperature exceeds

•Check refrigerant circuit

 

 

 

 

 

 

 

 

 

116°C during operation.

and refrigerant amount.

 

 

 

 

 

 

 

 

 

Compressor can restart if discharge

• Refer to 10-6.G"Check

 

 

 

 

 

 

 

 

 

temperature thermistor reads 100: or

of LEV".

 

 

 

 

 

 

 

 

 

less 3 minutes later.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6-time flash

High pressure

Lighting

Lighting

When the outdoor heat exchanger

•Check refrigerant circuit

 

 

 

 

 

 

 

 

 

temperature exceeds 70:

and refrigerant amount.

 

 

 

 

 

 

 

 

 

during cooling or the indoor gas

• Check the stop valve.

 

 

 

 

 

 

 

 

 

pipe temperature exceeds 70:

 

 

 

 

 

 

 

 

 

 

 

 

during heating.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7-time flash

Fin temperature

3 times

Goes

When the fin temperature exceeds

• Check around outdoor

 

 

 

 

 

 

 

 

out

87: during operation.

unit.

 

 

 

 

 

 

 

 

 

 

 

 

• Check outdoor unit air

 

 

 

 

 

 

 

 

 

 

 

 

passage.

 

 

 

 

 

 

 

 

 

 

 

 

• Refer to 10-6.D"Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board temperature

4 times

Goes

When the P.C. board temperature

of outdoor fan motor".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

out

exceeds 70: during operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-time flash

Outdoor fan motor

Lighting

Lighting

When failure occurs continuously

• Refer to 10-6.D"Check

 

 

 

 

 

 

 

 

 

three times within 30 seconds after

of outdoor fan motor".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the fan gets started.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9-time flash

Nonvolatile memory data

Lighting

5 times

When nonvolatile memory data

• Replace the outdoor

 

 

 

 

 

electronic control

 

 

 

 

 

 

 

 

 

cannot be read properly.

 

 

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-time flash

Discharge temperature

Lighting

Lighting

When the frequency of the

•Check refrigerant circuit

 

 

 

 

 

 

 

 

 

compressor is kept 80Hz or

and refrigerant amount.

 

 

 

 

 

 

 

 

 

more and the discharge

• Refer to 10-6.G"Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature is kept under 39:

of LEV".

 

 

 

 

 

 

 

 

 

for more than 20 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-4.).