No. | Symptom | Indication |
| Abnormal point / Condition | Condition | Correspondence | |
LED1(Red) | LED2(Yellow) |
| |||||
|
|
|
|
|
| ||
20 | Outdoor unit | Once | Lighting |
| Primary current protection | When the input current exceeds 15A. | These symptoms do not mean any abnormality of the |
operates. |
|
|
| product, but check the following points. | |||
| Secondary current protection | When the current of the compressor exceeds 15A. | |||||
|
|
|
|
| |||
|
|
|
|
| • Check if indoor filters are clogged. | ||
|
|
|
|
|
|
| |
|
| Twice | Lighting |
| When the indoor gas pipe temperature exceeds 45: during heating. | • Check if refrigerant is short. | |
21 |
|
|
|
| • Check if indoor/outdoor unit air circulation is short cycled. | ||
|
|
|
| Defrosting in cooling | When the indoor gas pipe temperature falls 3: or below during cooling. | ||
|
|
|
|
| |||
|
|
|
|
|
| ||
22 |
| 3 times | Lighting |
| Discharge temperature |
| • Check refrigerant circuit and refrigerant amount. |
|
| When the discharge temperature exceeds 100: during operation. | • Refer to | ||||
|
| protection | |||||
|
|
|
|
|
| • Refer to | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Low discharge | When the frequency of the compressor is kept 80Hz or more and | • Refer to |
23 |
| 4 times | Lighting |
| the discharge temperature is kept under 39: for more than 20 | ||
|
| temperature protection | • Check refrigerant circuit and refrigerant amount. | ||||
|
|
|
|
| minutes. | ||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| This symptom does not mean any abnormality of the |
|
|
|
|
| Cooling | When the outdoor heat exchanger temperature exceeds 58: | product, but check the following points. |
24 |
| 5 times | Lighting |
| • Check if indoor filters are clogged. | ||
|
| protection | during operation. | ||||
|
| • Check if refrigerant is short. | |||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| • Check if indoor/outdoor unit air circulation is short cycled. |
|
|
|
|
|
|
|
|
| Outdoor unit |
|
|
|
|
|
|
25 | operates | 9 times | Lighting |
| Inverter check mode | When the unit is operated with emergency operation switch. | - |
26
Lighting
Lighting
Normal
-
-
22