10-6. Troubleshooting flow
MUZ-GB50VA
A How to check inverter/ compressor
Disconnect the terminal of the compressor. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION.
|
|
| W • After the outdoor fan starts running, wait for 1 minutes or more before | ||||||||
|
|
| |||||||||
Measure the voltage between each |
| measuring the voltage. |
| ||||||||
lead wire leading to the compressor. |
| • The output voltage values have the tolerance of i20%. |
| ||||||||
U (BLK) - V (WHT) |
| No |
| ||||||||
V (WHT) - W (RED) |
|
|
|
|
|
|
|
| COOL | HEAT | |
W (RED) - U (BLK) |
|
|
|
|
|
|
|
| |||
Is voltage output on right table? |
|
|
|
|
|
|
| 122V~154V | 74V~126V | ||
| Yes | No |
|
|
|
|
|
|
| (56Hz~71Hz) | (30Hz~58Hz) |
| |||||||||||
Is output balanced? |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Is the input voltage to the outdoor electronic No |
|
|
|
|
| ||||||
|
|
|
| ||||||||
control P.C. board 370V or more? |
|
|
| Replace the power board. |
| ||||||
|
|
| |||||||||
|
|
|
|
|
|
|
|
| |||
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Turn off power supply of indoor and outdoor unit, |
| ||||||||||
and measure the compressor winding resistance No |
| ||||||||||
between the compressor terminals. |
|
|
|
|
|
|
|
|
| ||
Is the resistance between each terminal normal? |
|
| |||||||||
| Yes |
|
|
|
|
|
|
| Replace the |
| |
|
|
|
|
|
|
|
| compressor. |
| ||
|
|
|
|
|
|
|
|
|
|
Reconnect the lead wire of compressor, and turn on power supply to indoor and outdoor unit.
3 minutes later, starts EMERGENCY OPERATION.
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
24