7
REFRIGERANT SYSTEM DIAGRAM
MUZ-GB50VA
OUTDOOR UNIT
Unit:mm
Muffler
Refrigerant pipe [12.7 |
|
|
|
|
|
|
(with heat insulator) |
|
|
|
|
|
|
Stop valve |
|
|
|
|
|
|
(with service port) |
|
| Outdoor |
|
| |
Flared connection | Discharge |
|
|
|
| |
|
| heat |
| Ambient | ||
| temperature | Defrost | exchanger | temperature | ||
| thermistor |
|
|
| thermistor | |
| RT62 |
| thermistor |
|
| RT65 |
|
|
| RT61 |
|
|
|
| Compressor |
|
|
| ||
|
|
|
| Outdoor heat |
| |
|
|
|
| exchanger |
|
|
|
|
|
| temperature |
| |
|
|
|
| thermistor |
|
|
Flared connection |
|
|
| RT68 |
|
|
Strainer | LEV |
| R.V. coil |
|
| |
| Strainer | Refrigerant flow in cooling | ||||
Receiver #100 |
| #100 | OFF | |||
|
|
|
| ON | Refrigerant flow in heating | |
Stop valve | Capillary tube |
|
|
|
|
|
Refrigerant pipe [6.35 | [3.6✕[2.4✕50 |
|
|
|
| |
|
|
|
|
|
| |
(with heat insulator) |
|
|
|
|
|
|
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
|
| Refrigerant piping : m | Piping size O.D : mm | ||
Model |
|
|
| ||
Max. length |
| Max. Height difference | |||
|
|
| |||
|
|
|
|
|
|
| A |
| B | Gas | Liquid |
30 |
| 15 | 12.7 | 6.35 | |
|
|
|
|
|
|
Indoor unit
Max. Height
difference
B
Max. length
A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Model | Outdoor unit |
|
| Refrigerant piping length (one way) |
|
| |||
|
|
|
|
|
|
|
| ||
precharged | 7m | 10m |
| 15m | 20m |
| 25m | 30m | |
|
|
| |||||||
1,500 | 0 | 60 |
| 160 | 260 |
| 360 | 460 | |
|
|
|
|
|
|
|
|
|
|
Calculation : Xg=20g/m ✕ (Refrigerant piping length
NOTE : Refrigerant piping exceeding 7m requires additional refrigerant charge according to the calculation.
8