Mitsubishi Electronics MUZ-GB50VA service manual Refrigerant System Diagram, Unitmm

Models: MUZ-GB50VA

1 40
Download 40 pages 20.25 Kb
Page 8
Image 8

7

REFRIGERANT SYSTEM DIAGRAM

MUZ-GB50VA

OUTDOOR UNIT

Unit:mm

Muffler 4-way valve #100

Refrigerant pipe [12.7

 

 

 

 

 

 

(with heat insulator)

 

 

 

 

 

 

Stop valve

 

 

 

 

 

 

(with service port)

 

 

Outdoor

 

 

Flared connection

Discharge

 

 

 

 

 

 

heat

 

Ambient

 

temperature

Defrost

exchanger

temperature

 

thermistor

 

 

 

thermistor

 

RT62

 

thermistor

 

 

RT65

 

 

 

RT61

 

 

 

 

Compressor

 

 

 

 

 

 

 

Outdoor heat

 

 

 

 

 

exchanger

 

 

 

 

 

 

temperature

 

 

 

 

 

thermistor

 

 

Flared connection

 

 

 

RT68

 

 

Strainer

LEV

 

R.V. coil

 

 

 

Strainer

Refrigerant flow in cooling

Receiver #100

 

#100

OFF

 

 

 

 

ON

Refrigerant flow in heating

Stop valve

Capillary tube

 

 

 

 

 

Refrigerant pipe [6.35

[3.6[2.450

 

 

 

 

 

 

 

 

 

 

(with heat insulator)

 

 

 

 

 

 

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE

 

 

Refrigerant piping : m

Piping size O.D : mm

Model

 

 

 

Max. length

 

Max. Height difference

 

 

 

 

 

 

 

 

 

 

A

 

B

Gas

Liquid

MUZ-GB50VA

30

 

15

12.7

6.35

 

 

 

 

 

 

Indoor unit

Max. Height

difference

B

Max. length

A

Outdoor unit

ADDITIONAL REFRIGERANT CHARGE (R410A:g)

Model

Outdoor unit

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

 

 

 

 

precharged

7m

10m

 

15m

20m

 

25m

30m

 

 

 

MUZ-GB50VA

1,500

0

60

 

160

260

 

360

460

 

 

 

 

 

 

 

 

 

 

Calculation : Xg=20g/m (Refrigerant piping length (m)–7)

NOTE : Refrigerant piping exceeding 7m requires additional refrigerant charge according to the calculation.

8

Page 8
Image 8
Mitsubishi Electronics MUZ-GB50VA service manual Refrigerant System Diagram, Unitmm